Inspection Detail
Inspection: 300494234 - Cunningham And Smith Inc. Dba Waterworks Car Wash
Inspection Information - Office: Fort Lauderdale Area Office
Site Address:
Cunningham And Smith Inc. Dba Waterworks Car Wash
1101 20 St
Vero Beach, FL 32960
Mailing Address:
3306 N. U.S. 1, Vero Beach, FL 32960
Union Status: NonUnion
SIC:7542
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Health
Close Conference: 08/20/1997
Emphasis:
Case Closed: 02/13/1998
Type | Activity Nr | Safety | Health |
---|---|---|---|
Accident | 100670975 |
Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
---|---|---|---|---|---|---|
Initial Violations | 2 | 2 | ||||
Current Violations | 2 | 2 | ||||
Initial Penalty | $2,250 | $0 | $0 | $0 | $0 | $2,250 |
Current Penalty | $2,250 | $0 | $0 | $0 | $0 | $2,250 |
FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
# | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
---|---|---|---|---|---|---|---|---|---|---|---|
1. | 01001 | Serious | 19100304 F05 IVB | 10/29/1997 | 11/03/1997 | $1,500 | $1,500 | $0 | - | ||
2. | 01002 | Serious | 19100305 G01 III | 10/29/1997 | 11/03/1997 | $750 | $750 | $0 | - |
Investigation Summary
An employee was working in an equipment room at a car wash. He was electrocuted when he contacted the metal frame of some electric equipment. The metal frame of the equipment, which was not connected to an equipment grounding conductor, was energized by a ground fault. Flexible cords had been used in lieu of fixed wiring to supply current to the equipment. A faulty attachment plug was believed to be the cause of the ground fault.
Keywords: ELECTRICAL, ELECTROCUTED, ATTACHMENT PLUG, GROUND FAULT, EQUIPMENT GROUNDING, ELECTRIC CORD, ELEC EQUIPMENT--MISC
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 300494234 | Fatality | Electric Shock | Miscellaneous plant and system operators |