Inspection Detail
Inspection: 300455631 - Teledyne Industries Inc
Inspection Information - Office: Tennessee Osha Nashville Office - Safety
Site Address:
Teledyne Industries Inc
One Teledyne Place
La Vergne, TN 37086
Mailing Address:
, , 00000
Union Status: NonUnion
SIC:3545
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 12/04/1997
Planning Guide: Safety-Manufacturing
Emphasis:
Case Closed: 01/27/2000
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 361012297 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 3 | 3 | ||||
| Current Violations | 3 | 3 | ||||
| Initial Penalty | $15,000 | $0 | $0 | $0 | $0 | $15,000 |
| Current Penalty | $7,500 | $0 | $0 | $0 | $0 | $7,500 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Serious | 19100332 B01 | 02/04/1998 | 04/22/1999 | $2,500 | $5,000 | $0 | F - Formal Settlement | ||
| 2. | 01002 | Serious | 19100333 B02 | 02/04/1998 | 03/13/1998 | $2,500 | $5,000 | $0 | F - Formal Settlement | ||
| 3. | 01003A | Serious | 19100333 B02 I | 02/04/1998 | 04/22/1998 | $2,500 | $5,000 | $0 | F - Formal Settlement | ||
| 4. | 01003B | Serious | 19100333 B02 IIA | 02/04/1998 | 04/22/1998 | $0 | $0 | $0 | F - Formal Settlement |
Investigation Summary
An electrician working the night shift at a metal working plant was instructed to rewire the cooling fan motor on a furnace. He was to reconnect the motor supply conductors to a 480/277-volt line that serviced an adjacent furnace. The second furnace was in operation while the electrician was performing this task. Standing on a 1.8-meter ladder, the employee ran the motor supply conductors through a section of metal conduit. He then started connecting the conductors to their terminals. When he connected the first conductor to an energized terminal, the other two conductors became energized by backfeed through the load at the second furnace. He was using a screwdriver and wire strippers. He grabbed the second conductor, cut into it with the wire stripper, and was electrocuted.
Keywords: VOLTAGE BACKFEED, E GI IV, ELECTRICAL, ELECTRICIAN, ELECTROCUTED, ELECTRICAL WORK, LOCKOUT, ELECTRIC CONDUCTOR
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 300455631 | Fatality | Electric Shock | Electricians |