Inspection Detail
Inspection: 3004322 - City Of Raleigh, Parks And Recreation Department
Inspection Information - Office: Nc Department Of Labor - Raleigh
Site Address:
City Of Raleigh, Parks And Recreation Department
Pullen Park Pool, 520 Ashe Avenue
Raleigh, NC 27606
Mailing Address:
2401 Wade Avenue, Raleigh, NC 27607
Union Status: NonUnion
SIC:7999
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: LocalGovt
Safety/Health: Health
Close Conference: 08/26/1988
Emphasis:
Case Closed: 06/12/1991
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 360263719 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 6 | 6 | ||||
| Current Violations | 6 | 6 | ||||
| Initial Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| Current Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Other | 7C0101 A99 F4 | 02/22/1989 | 02/28/1989 | $0 | $0 | $0 | - | ||
| 2. | 01002 | Other | 19100037 Q01 | 02/22/1989 | 02/28/1989 | $0 | $0 | $0 | - | ||
| 3. | 01003 | Other | 19100037 Q02 | 02/22/1989 | 02/28/1989 | $0 | $0 | $0 | - | ||
| 4. | 01004 | Other | 19100037 Q08 | 02/22/1989 | 02/28/1989 | $0 | $0 | $0 | - | ||
| 5. | 01005 | Other | 19100303 F | 02/22/1989 | 02/28/1989 | $0 | $0 | $0 | - | ||
| 6. | 01006 | Other | 19100305 B01 | 02/22/1989 | 02/28/1989 | $0 | $0 | $0 | - |
Investigation Summary
Between 11:00 and 11:30 a.m. on August 17, 1989, at Pullen Park, the main circulation pump of the pool stopped for unknown reasons. When the pump stopped, the Delaval switch on the Strantrol 390 chemical monitoring unit failed to sense the loss of water pressure, thus allowing hydrochloric acid and sodium hypochlorite to be admitted to a closed, static piping system. Approximately 3 liters of hydrochloric acid and 6 liters of sodium hypochlorite were added, forming approximately 322 liters of chlorine gas. Employee #3 started the circulation pump at approximately 11:30 a.m., pushing water and chlorine gas into the pool. The gas came out of the solution, forming a vapor cloud that dissipated after approximately 20 minutes. Approximately 50 patrons, five pool staff (four lifeguards and the assistant manager), and six administrative staff were on site. The pool staff were performing their normal duties, while the others were on the site to inspect/evaluate the building's electrical system. All persons were evacuated from the pool by the locker rooms or pool office through the main entrance to the outside. Thirty-two patrons and Employees #1, #2, and #3 (two lifeguards and one administrative staff member) were treated by EMS and sent to the hospital for observation of minor lung irritation. No employees were admitted, but six patrons were hospitalized.
Keywords: LUNG, VAPOR, INHALATION, EQUIPMENT FAILURE, CHLORINE, POOL, CHEMICAL REACTION, TOXIC FUMES, PUMP
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 3004322 | Non Hospitalized injury | Other | Protective service occupations, n.e.c. | ||
| 2 | 3004322 | Non Hospitalized injury | Other | Protective service occupations, n.e.c. | ||
| 3 | 3004322 | Non Hospitalized injury | Other | Protective service occupations, n.e.c. |
Translate