Inspection Detail
Inspection: 300215712 - Mayol Plumbing & Heating, Inc.
Inspection Information - Office: Peoria Area Office
Site Address:
Mayol Plumbing & Heating, Inc.
305 Pine St.
Normal, IL 61761
Mailing Address:
1003 1/2 Lafayette, Bloomington, IL 61701
Union Status: NonUnion
SIC:1711
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 05/01/1997
Planning Guide: Safety-Construction
Emphasis:
Case Closed: 10/22/1997
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 100270123 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 1 | 1 | ||||
| Current Violations | 1 | 1 | ||||
| Initial Penalty | $1,500 | $0 | $0 | $0 | $0 | $1,500 |
| Current Penalty | $1,000 | $0 | $0 | $0 | $0 | $1,000 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001A | Serious | 19260404 B01 I | 05/08/1997 | 05/13/1997 | $1,000 | $1,500 | $0 | 05/29/1997 | F - Formal Settlement | |
| 2. | 01001B | Serious | 19260404 F06 | 05/08/1997 | 05/13/1997 | $0 | $0 | $0 | 05/29/1997 | F - Formal Settlement |
Investigation Summary
An employee was replacing water pipes in an old apartment building. He was using a trouble light as an extension cord set to provide power to a Sawzall. The apartment where the repairs were being made was not wired with an equipment grounding conductor, and the receptacles in the apartment would not accept a grounding prong. Additionally, the equipment grounding prong on the trouble light's power supply cord had been removed. The employee placed the trouble light, which had a metal guard that had apparently been energized by a ground fault, on an aluminum ladder. The employee was electrocuted when he contacted the ladder with his right arm while his right temple was touching a copper water pipe.
Keywords: E GI V, ELECTRICAL, ELECTROCUTED, GROUND FAULT, EQUIPMENT GROUNDING, ELECTRIC LIGHT--PORT
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 300215712 | Fatality | Electric Shock | Plumbers, pipefitters and steamfitters |
Translate