Inspection Detail
Inspection: 2981835 - Denny Plywood Company
Inspection Information - Office: Nc Department Of Labor - Raleigh
Site Address:
Denny Plywood Company
310 South East St.
Roseboro, NC 28382
Mailing Address:
Post Office Box 356, Roseboro, NC 28382
Union Status: NonUnion
SIC:2435
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 04/18/1988
Emphasis:
Case Closed: 06/21/1988
Type | Activity Nr | Safety | Health |
---|---|---|---|
Accident | 360262141 |
Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
---|---|---|---|---|---|---|
Initial Violations | 1 | 1 | ||||
Current Violations | 1 | 1 | ||||
Initial Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
Current Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
# | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
---|---|---|---|---|---|---|---|---|---|---|---|
1. | 01001 | Other | 19100157 G01 | 05/19/1988 | 06/21/1988 | $0 | $0 | $0 | - |
Investigation Summary
SMOKE WAS SEEN COMING FROM ONE OF THE FLEXIBLE DUCTS OF A PRODUCTION BELT SANDER. THE SANDER WAS SHUT DOWN AND THE COVER OPENED TO DETERMINE THE CAUSE OF THE SMOKE. A SMALL FIRE WAS DISCOVERED INSIDE THE SANDER IN SOME ACCUMULATED WOOD DUST. PLANT PERSONNEL EXTINGUISHED THE FIRE. AFTER THIS FIRE WAS EXTINGUISHED, SMOKE WAS DETECTED COMING FROM THE DUST COLLECTION SYSTEM PIPE OUTSIDE THE PLANT. INVESTIGATION REVEALED THAT THERE WAS SOME DUST ON FIRE INSIDE THE PIPE NEAR THE CYCLONE. A HOLE WAS CUT IN THE PIPE AND WATER DIRECTED ONTO THE FIRE. DURING THIS TIME, THE EXHAUST SYSTEM BLOWER WAS TURNED OFF. WHILE THE WATER WAS BEING PLACED ONTO THE FIRE IN THE PIPE, AN EMPLOYEE WAS BANGING ON THE PIPE TRYING TO DISLODGE THE BURNING DUST. WHEN THE BLOWER WAS TURNED BACK ON, THE DUST IN THE PIPE EXPLODED, RUPTURING THE PIPE IN SEVERAL PLACES. EMPLOYEES #1 AND #2 WERE STANDING NEAR THE RUPTURE POINTS. THEY RECEIVED SEVERAL FIRST DEGREE BURNS FROM THE FLASH FIRE. ONE EMPLOYEE RECEIVED SMALL PATCHES OF SECOND DEGREE BURNS ON ONE ARM.
Keywords: BURN, SANDING MACHINE, DUCT, DUST, BELT, FIRE, DUST COLLECTOR, EXPLOSION, PIPE, ARM
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 2981835 | Non Hospitalized injury | Burn/Scald(Heat) | Managers and administrators, n.e.c | ||
2 | 2981835 | Non Hospitalized injury | Burn/Scald(Heat) | Supervisors, production occupations |