Powered by GoogleTranslate

Inspection Detail

Inspection: 2937951 - Nevada Power Company

Inspection Information - Office: Nv-E-Las Vegas 0953220

 

Inspection Nr: 2937951
Report ID: 0953220
Date Opened: 06/26/1985

Site Address:
Nevada Power Company
111 Maryland Pkwy
Las Vegas, NV 89101

Mailing Address:
Po Box 230, Las Vegas, NV 89151

Union Status: Union

SIC:4911

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 07/12/1985

Emphasis:

Case Closed: 07/15/1985


Related Activity
Type Activity Nr Safety Health
Accident 36064095

Investigation Summary

Investigation Nr: 14236087
Event: 06/17/1985
Electric Shock - Direct Contact with Overhead Line

Two employees were transferring overhead power lines from one utility pole to another. The new pole was 45 feet high with 3-foot-wide crossarms. The existing poles on each side of the new one were 39 feet high with 8-foot-wide crossarms. The employees had to bring the conductor on which they were working inward 5 feet and raise it 6 feet. The two employees were working from an insulated aerial lift. Using hot sticks, they placed the energized power line in a temporary position on the crossarm. One of the workers put down his hot stick so that he could secure the conductor to the crossarm. The other employee, who was still holding the line with his hot stick, heard a loud thud. The conductor started shaking violently and came off the crossarm. It then struck the first employee on the shoulder. He received a fatal electric shock. It was believed that a guy was hit somewhere along the line, causing the conductor to shake off the crossarm. Additionally, the first section of the boom of the aerial lift was fully retracted. In this position, the aerial lift was not insulated. This allowed current to flow through the employee to the boom of the lift and to ground.

Keywords: OVERHEAD POWER LINE, ELECTRICAL, POWER LINE WORKER, ELECTROCUTED, E PTD, ELEC UTILITY WORK, UTILITY POLE, AERIAL LIFT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 2937951 Fatality Electric Shock Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.