Powered by GoogleTranslate

Inspection Detail

Case Status: CLOSED

Inspection: 281477.015 - K & E Electric Inc

Inspection Information - Office: Chicago South Area Office

 

Inspection Nr: 281477.015
Report ID: 0521700
Date Opened: 03/15/2012

Site Address:
K & E Electric Inc
303 W. Madison
Chicago, IL 60601

Mailing Address:
1419 Garden St., Park Ridge, IL 60068

Union Status: NonUnion

SIC:

NAICS: 238210/Electrical Contractors


Inspection Type: Fat/Cat

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 03/15/2012

Emphasis:

Case Closed: 09/07/2012


Related Activity
Type Activity Nr Safety Health
Accident 217824
Case Status: CLOSED
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 2
Current Violations 1 1
Initial Penalty $8,400 $0 $0 $0 $0 $8,400
Current Penalty $2,100 $0 $0 $0 $0 $2,100
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citation Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001A Serious 19260416 A01 07/12/2012 07/19/2012 $2,100 $4,200 $0 I - Informal Settlement  
2. 01001B Serious 19260417 B 07/12/2012 07/19/2012 $0 $4,200 $0 I - Informal Settlement  

Investigation Summary

Investigation Nr: 10792.015
Event: 03/15/2012
Employee is electrocuted while installing transformer to var

At 2:00 a.m. on March 15, 2012, an employee and a coworker were retrofitting the HVAC system with a new variable air volume (VAV) control box with electrical controls. The employee accessed the air unit that was located above a drop down ceiling. The employee was working alone on the 25th floor of the building atop of a frame ladder. While installing VAV boxes to the HVAC unit, the employee followed the protocol in place in which the local electrical interrupter (switch) located on the HVAC unit was used to de-energize the unit. The switch shut off power to the unit, however, there was a 277 volt line coming into the switch. The employee contacted the live electrical parts and was electrocuted. He fell from his ladder onto the ground of the 25th floor. At 2:05 a.m., the coworker returned to the 25th floor to find the employee lying on the floor next to the ladder and unresponsive. The coworker called the emergency medical services and the employee was transported to a local hospital. The employee was killed by an electric shock.

Keywords: Electric Shock, Electrical, Electrical Box, Electrician, Electrocuted

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 281477.015 47 M Fatality Electricians
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.