Powered by GoogleTranslate

Inspection Detail

Inspection: 2809788 - Weis Market, Inc.

Inspection Information - Office: Department Of Labor, Licensing, And Regulation Division Of Labor And Industry Maryland Occupational Safety And Health

 

Inspection Nr: 2809788
Report ID: 0352420
Date Opened: 08/22/1986

Site Address:
Weis Market, Inc.
1161 Maryland Avenue
Baltimore, MD 21740

Mailing Address:
1000 S. Second T., Sunbury, PA 17801

Union Status: NonUnion

SIC:5411

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 08/27/1986

Emphasis:

Case Closed: 09/29/1986


Related Activity
Type Activity Nr Safety Health
Accident 360749196

Investigation Summary

Investigation Nr: 14457386
Event: 08/21/1986
BURNS - GROUND FAULT IN PANELBOARD

A REFRIGERATION AND MAINTENANCE MECHANIC FOR AREA STORES WAS CALLED TO CHECK ON AN ELECTRICAL PROBLEM. THE EMPLOYEE FOUND THAT ONE OF THE PHASES OF THE THREE-PHASE SYSTEM WAS INOPERATIVE, CAUSING THE REFRIGERATION COMPRESSORS TO SHUT DOWN. SINCE THE OTHER TWO PHASES WERE STILL ENERGIZED, THE COMPRESSORS WERE TRYING TO RESTART, RESULTING IN A LARGE AMOUNT OF HEAT BUILD-UP WITHIN THE EQUIPMENT. THE EMPLOYEE TURNED OFF ALL THE BREAKERS AND HAD THE ELECTRIC UTILITY COMPANY COME OUT TO REPAIR THE INOPERATIVE PHASE. ONCE THE PHASE WAS REPAIRED, THE EMPLOYEE TURNED ON ALL THE CIRCUIT BREAKERS TO RESTORE POWER TO THE COMPRESSORS. ALL THE BREAKERS BUT ONE COULD BE RESET. THE EMPLOYEE OBTAINED A REPLACEMENT BREAKER AND ATTEMPTED TO INSTALL IT, BUT IT WOULD NOT FIT INTO THE PANEL. THE EMPLOYEE DECIDED TO OBTAIN A NEW BREAKER THE NEXT DAY AND TRY TO INSTALL IT. THE NEXT DAY, A NEW 70-AMPERE, 3-PHASE BREAKER WAS OBTAINED. THIS BREAKER ALSO WOULD NOT FIT INTO THE PANEL EVEN THOUGH IT WAS THE PROPER BREAKER. THE EMPLOYEE ATTEMPTED TO REALIGN THE BUSBAR WITH A PIECE OF INSULATED MATERIAL. THE BUSBAR SHORTED TO GROUND, CAUSING A FLASH AND FIRE. THE EMPLOYEE RECEIVED BURNS ON HIS HANDS. THE PANELBOARD WAS A 240-VOLT, 3-PHASE UNIT. THE EMPLOYEE HAD RECEIVED TRADE SCHOOL TRAINING AND ATTENDED PERIODIC SEMINARS. HE NORMALLY WORKED ALONE.

Keywords: BURN, E GI III, ELECTRICAL, FIRE, PANELBOARD, BUSBAR, ELECTRICAL WORK, GROUND FAULT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 2809788 Non Hospitalized injury Burn/Scald(Heat) Heating, air conditioning, and refrig. mechanics
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.