Powered by GoogleTranslate

Inspection Detail

Inspection: 2585974 - Citizens Utilities Company

Inspection Information - Office: Arizona Division Of Occupational Safety And Health (Adosh)

 

Inspection Nr: 2585974
Report ID: 0950411
Date Opened: 07/18/1986

Site Address:
Citizens Utilities Company
Jct. I-19 & Hwy. 189
Nogales, AZ 85621

Mailing Address:
, , 00000

Union Status: NonUnion

SIC:4911

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 07/21/1986

Emphasis:

Case Closed: 07/31/1986


Related Activity
Type Activity Nr Safety Health
Accident 360578884

Investigation Summary

Investigation Nr: 14565840
Event: 07/17/1986
ELECTRIC SHOCK - CONTACT WITH OVERHEAD LINE THRU CONDUCTOR

Two power line workers were on an emergency service call responding to a power outage. It was raining, and a guy had broken and fallen on an overhead power line. One of the three phase conductors of the 13-kilovolt power line had burned in two. The fuse protecting the line had opened. Before beginning work on this line, the two employees deenergized the other two phase conductors on the line by opening their cutouts. The employees spliced the broken conductor while they were on the ground. They then started taking out the slack in the conductor by pulling on it and sending it up to a third power line worker who was on a utility pole. The energized part of the cutout contacted the end of the downed conductor, energizing it. Both of the employees on the ground were touching the now energized conductor. One of them was electrocuted. The other received an electric shock and severe burns on his chest and the lower section of his body. He was hospitalized for his injuries.

Keywords: BURN, OVERHEAD POWER LINE, PROTECTIVE GROUNDING, ELECTRICAL, POWER LINE WORKER, ELECTROCUTED, LOCKOUT, E PTD, ELEC UTILITY WORK, ELECTRIC SHOCK

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 2585974 Fatality Electric Shock Electrical power installers and repairers
2 2585974 Hospitalized injury Electric Shock Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.