Inspection Detail
Inspection: 2585974 - Citizens Utilities Company
Inspection Information - Office: Arizona Division Of Occupational Safety And Health (Adosh)
Site Address:
Citizens Utilities Company
Jct. I-19 & Hwy. 189
Nogales, AZ 85621
Mailing Address:
, , 00000
Union Status: NonUnion
SIC:4911
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 07/21/1986
Emphasis:
Case Closed: 07/31/1986
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 360578884 |
Investigation Summary
Two power line workers were on an emergency service call responding to a power outage. It was raining, and a guy had broken and fallen on an overhead power line. One of the three phase conductors of the 13-kilovolt power line had burned in two. The fuse protecting the line had opened. Before beginning work on this line, the two employees deenergized the other two phase conductors on the line by opening their cutouts. The employees spliced the broken conductor while they were on the ground. They then started taking out the slack in the conductor by pulling on it and sending it up to a third power line worker who was on a utility pole. The energized part of the cutout contacted the end of the downed conductor, energizing it. Both of the employees on the ground were touching the now energized conductor. One of them was electrocuted. The other received an electric shock and severe burns on his chest and the lower section of his body. He was hospitalized for his injuries.
Keywords: BURN, OVERHEAD POWER LINE, PROTECTIVE GROUNDING, ELECTRICAL, POWER LINE WORKER, ELECTROCUTED, LOCKOUT, E PTD, ELEC UTILITY WORK, ELECTRIC SHOCK
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 2585974 | Fatality | Electric Shock | Electrical power installers and repairers | ||
| 2 | 2585974 | Hospitalized injury | Electric Shock | Electrical power installers and repairers |