Powered by GoogleTranslate

Inspection Detail

Inspection: 2448892 - Saqulpa Tank Company Inc

Inspection Information - Office: Oklahoma City Area Office

 

Inspection Nr: 2448892
Report ID: 0627700
Date Opened: 05/15/1985

Site Address:
Saqulpa Tank Company Inc
1/4 Mile East Of I 35 On Airline Road
Pauls Valley, OK 73075

Mailing Address:
Po Box 1204, Sapulpa, OK 74066

Union Status: NonUnion

SIC:1791

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 05/15/1985

Planning Guide: Safety-Construction

Emphasis:

Case Closed: 11/19/1985


Related Activity
Type Activity Nr Safety Health
Accident 360642474
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $720 $0 $0 $0 $0 $720
Current Penalty $360 $0 $0 $0 $0 $360
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001A Serious 19260021 B02 09/27/1985 09/30/1985 $360 $720 $0 I - Informal Settlement  
2. 01001B Serious 19260401 A01 09/27/1985 09/30/1985 $0 $0 $0 -  

Investigation Summary

Investigation Nr: 14495600
Event: 05/13/1985
ELECTRIC SHOCK - GROUND FAULT IN PANELBOARD

A CREW OF EMPLOYEES WAS ERECTING A WATER TOWER. THEY WERE USING A 480-VOLT, 3-PHASE, 210-KILOWATT CATERPILLAR GENERATOR (MODEL NUMBER SR-4) TO SUPPLY POWER TO A JOY AIR COMPRESSOR. THE COMPRESSOR WAS CONNECTED TO A PANELBOARD BY A LABORER AS DIRECTED BY THE FOREMAN. THE LABORER WIRED THE PANELBOARD INCORRECTLY, AND THE WIRING FAULT ENERGIZED THE FRAME OF THE AIR COMPRESSOR. HEAVY RAINS EARLIER IN THE DAY HAD LEFT WATER STANDING UP TO 2 INCHES DEEP AROUND THE COMPRESSOR. THE FOREMAN WALKED BY THE COMPRESSOR TO RETRIEVE SOME EQUIPMENT. WHEN HE STEPPED IN THE WATER, HE WAS ELECTROCUTED.

Keywords: ELECTRICAL, ELECTROCUTED, PANELBOARD, ELECTRICAL WORK, E C, GROUND FAULT, EQUIPMENT GROUNDING, UNTRAINED, WATER

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 2448892 Fatality Electric Shock Supervisors, n.e.c.
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close