Powered by GoogleTranslate

Inspection Detail

Inspection: 2436939 - Fitts Electrical Construction Co., Inc.

Inspection Information - Office: Lubbock Area Office

 

Inspection Nr: 2436939
Report ID: 0627400
Date Opened: 03/15/1988

Site Address:
Fitts Electrical Construction Co., Inc.
16 Mi. Ne Of Andrews, Texas
Andrews, TX 79714

Mailing Address:
P. O. Box 1248, Andrews, TX 79714

Union Status: NonUnion

SIC:1623

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: Y

Ownership: Private

Safety/Health: Safety

Close Conference: 03/16/1988

Emphasis: L:Oilgas

Case Closed: 06/01/1988


Related Activity
Type Activity Nr Safety Health
Accident 360155733
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 5 5
Current Violations 5 5
Initial Penalty $0 $0 $0 $0 $0 $0
Current Penalty $0 $0 $0 $0 $0 $0
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other 19030002 A01 04/20/1988 04/23/1988 $0 $0 $0 -  
2. 01002 Other 19040007 04/20/1988 04/23/1988 $0 $0 $0 -  
3. 01003 Other 19040008 04/20/1988 04/23/1988 $0 $0 $0 -  
4. 01004 Other 19260050 C 04/20/1988 06/08/1988 $0 $0 $0 -  
5. 01005 Other 19260556 B02 V 04/20/1988 05/03/1988 $0 $0 $0 -  

Investigation Summary

Investigation Nr: 14493985
Event: 03/08/1988
ELECTRIC SHOCK - CONTACT WITH OVERHEAD LINE THRU GUY

A power line worker and a ground worker were sent to install a new anchor and guy on a utility pole. The employees were instructed to deenergize the line before beginning work. However, they did not do so. They installed the anchor, and the line worker got into an insulated aerial lift with the new down guy line dangling from the bucket to ground. The line worker ascended to the work area and picked up the guy. The guy contacted the outer phase conductor of the 7200-volt-to-ground power line, electrocuting the power line worker. (The ground worker heard the arcing and used the lower controls to bring the dead employee down.)

Keywords: ELEC PROTECT EQUIP, OVERHEAD POWER LINE, ELECTRICAL, POWER LINE WORKER, ELECTROCUTED, E PTD, GUY, ELEC UTILITY WORK, AERIAL LIFT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 2436939 Fatality Electric Shock Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close