Powered by GoogleTranslate

Inspection Detail

Inspection: 2264786 - Caravelle Pour Homme Ltd.

Inspection Information - Office: Parsippany Area Office

 

Inspection Nr: 2264786
Report ID: 0214200
Date Opened: 06/24/1986

Site Address:
Caravelle Pour Homme Ltd.
90 Caven Point Road
Jersey City, NJ 07305

Mailing Address:
, , 00000

Union Status: NonUnion

SIC:4225

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 07/02/1986

Emphasis:

Case Closed: 11/13/1986


Related Activity
Type Activity Nr Safety Health
Accident 360663371
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 2
Current Violations 2 2
Initial Penalty $800 $0 $0 $0 $0 $800
Current Penalty $440 $0 $0 $0 $0 $440
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19100026 A03 VIII 08/21/1986 08/29/1986 $220 $400 $0 I - Informal Settlement  
2. 01002 Serious 19100303 B01 08/21/1986 08/24/1986 $220 $400 $0 I - Informal Settlement  

Investigation Summary

Investigation Nr: 14480990
Event: 06/22/1986
ELECTRIC SHOCK - DIRECT CONTACT WITH ENERGIZED CONDUCTOR

A clothing store employee worked part time on Saturdays as a sales clerk and maintenance worker. One day he was assigned to move a three-phase, 120/240-volt, 200-ampere circuit breaker panelboard from an office hallway to a warehouse. He had finished connecting the panelboard to its supply conductors, and the panelboard was energized. He was on an aluminum ladder, working on a circuit supplying office hallway lighting. Standing on the fourth step of the ladder, he was working inside a 2.6-meter-high false ceiling where the junction boxes were located. The employee contacted an energized conductor and fell from the ladder. He died either from the electric shock or from injuries sustained in the fall.

Keywords: E GI II, ELEC PROTECT EQUIP, LIGHTING CIRCUIT, ELECTRICAL, LADDER, ELECTRICAL WORK, LOCKOUT, METAL LADDER, ELECTRIC SHOCK, FALL

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 2264786 Fatality Electric Shock Specified mechanics and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.