Inspection Detail
Inspection: 2204907 - Morton Chemical Division
Inspection Information - Office: Chicago North Area Office
Site Address:
Morton Chemical Division
2401 E. Pratt Blvd.
Elk Grove Village, IL 60007
Mailing Address:
, , 00000
Union Status: Union
SIC:2891
NAICS: 0
Inspection Type: Accident
Scope: Complete
Advanced Notice: N
Ownership: Private
Safety/Health: Health
Close Conference: 08/12/1986
Planning Guide: Health-Manufacturing
Emphasis:
Case Closed: 09/04/1987
Type | Activity Nr | Safety | Health |
---|---|---|---|
Referral | 900937152 | Yes |
Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
---|---|---|---|---|---|---|
Initial Violations | 3 | 1 | 5 | 9 | ||
Current Violations | 2 | 4 | 6 | |||
Initial Penalty | $1,300 | $0 | $1,000 | $0 | $0 | $2,300 |
Current Penalty | $710 | $0 | $0 | $0 | $0 | $710 |
FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
# | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
---|---|---|---|---|---|---|---|---|---|---|---|
1. | 01001A | Serious | 19101200 F01 II | 09/04/1986 | 09/04/1987 | $210 | $400 | $0 | P - Petition to Mod Abatement | ||
2. | 01001B | Serious | 19101200 F04 I | 09/04/1986 | 12/10/1986 | $0 | $0 | $0 | I - Informal Settlement | ||
3. | 01002 | Serious | 19101200 G02 VI | 09/04/1986 | 10/10/1986 | $400 | $400 | $0 | I - Informal Settlement | Citation has been deleted. | |
4. | 01003 | Serious | 19100106 E06 I | 09/26/1986 | 10/10/1986 | $500 | $500 | $0 | I - Informal Settlement | ||
5. | 02001 | Repeat | 19100106 E06 I | 09/04/1986 | 10/10/1986 | $1,000 | $1,000 | $0 | I - Informal Settlement | Citation has been deleted. | |
6. | 03001 | Other | 19101200 D02 | 09/04/1986 | 10/10/1986 | $0 | $0 | $0 | - | ||
7. | 03002 | Other | 19101200 E01 | 09/04/1986 | 10/10/1986 | $0 | $0 | $0 | I - Informal Settlement | Citation has been deleted. | |
8. | 03003 | Other | 19101200 F01 I | 09/04/1986 | 10/10/1986 | $0 | $0 | $0 | - | ||
9. | 03004 | Other | 19101200 H01 | 09/04/1986 | 10/10/1986 | $0 | $0 | $0 | - | ||
10. | 03005 | Other | 19101200 G02 VI | 09/26/1986 | 02/10/1987 | $0 | $0 | $0 | I - Informal Settlement |
Investigation Summary
Employee #1 was charging a 1,000-gallon mixing tank with dry materials prior to blending a batch of gel lacquer. Before charging, the tank had been cleaned with 50 gallons of toluene. The tank was charged through the top manhole opening using 370 pounds of a chlorinated rubber product and an estimated 120 pounds of carnauba wax. Employee #1 then removed the polyethylene liner from the fiberboard drum of wax and shook it. Shaking the polyethylene liner generated a static spark that ignited the dust and the toluene vapors in the tank. Fire flashed out of the tank and Employee #1 sustained first- and second-degree burns to 10 percent of his body. Nitrogen had been added to the tank, but sufficient oxygen was still present to support combustion.
Keywords: BURN, STATIC ELECTRICITY, FLAMMABLE VAPORS, WORK RULES, FIRE, TOLUENE, SPARK, CHEMICAL VAPOR, COMBUSTIBLE DUST, TANK
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 2204907 | Hospitalized injury | Burn/Scald(Heat) | Occupation not reported |