Inspection Detail
Inspection: 2116127 - Afc Cable
Inspection Information - Office: Marlton Area Office
Site Address:
Afc Cable
399 Dulty'S Lane
Burlington, NJ 08016
Mailing Address:
, , 00000
Union Status: NonUnion
SIC:3357
NAICS: 0
Inspection Type: Accident
Scope: Complete
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 01/12/1995
Planning Guide: Safety-Manufacturing
Emphasis:
Case Closed: 04/07/1995
Type | Activity Nr | Safety | Health |
---|---|---|---|
Accident | 360731194 |
Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
---|---|---|---|---|---|---|
Initial Violations | 8 | 4 | 12 | |||
Current Violations | 8 | 4 | 12 | |||
Initial Penalty | $23,400 | $0 | $0 | $2,000 | $0 | $25,400 |
Current Penalty | $18,400 | $0 | $0 | $1,000 | $0 | $19,400 |
FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
# | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
---|---|---|---|---|---|---|---|---|---|---|---|
1. | 01001 | Serious | 19100132 A | 02/06/1995 | 02/09/1995 | $3,500 | $4,500 | $0 | I - Informal Settlement | ||
2. | 01002A | Serious | 19100147 C04 II | 02/06/1995 | 03/11/1995 | $850 | $1,350 | $0 | I - Informal Settlement | ||
3. | 01002B | Serious | 19100333 B02 I | 02/06/1995 | 03/11/1995 | $0 | $0 | $0 | - | ||
4. | 01003 | Serious | 19100212 A01 | 02/06/1995 | 02/16/1995 | $850 | $1,350 | $0 | I - Informal Settlement | ||
5. | 01004 | Serious | 19100219 D01 | 02/06/1995 | 02/16/1995 | $850 | $1,350 | $0 | I - Informal Settlement | ||
6. | 01005 | Serious | 19100303 B01 | 02/06/1995 | 02/09/1995 | $3,500 | $4,500 | $0 | I - Informal Settlement | ||
7. | 01006 | Serious | 19100303 H03 | 02/06/1995 | 02/16/1995 | $4,500 | $4,500 | $0 | - | ||
8. | 01007 | Serious | 19100304 F04 | 02/06/1995 | 02/09/1995 | $850 | $1,350 | $0 | I - Informal Settlement | ||
9. | 01008 | Serious | 19100332 B01 | 02/06/1995 | 02/09/1995 | $3,500 | $4,500 | $0 | I - Informal Settlement | ||
10. | 02001 | Other | 19040002 A | 02/06/1995 | 02/23/1995 | $500 | $1,000 | $0 | I - Informal Settlement | ||
11. | 02002 | Other | 19040004 | 02/06/1995 | 02/23/1995 | $500 | $1,000 | $0 | I - Informal Settlement | ||
12. | 02003 | Other | 19100132 D01 | 02/06/1995 | 03/11/1995 | $0 | $0 | $0 | - | ||
13. | 02004 | Other | 19100132 F01 | 02/06/1995 | 03/11/1995 | $0 | $0 | $0 | - |
Investigation Summary
An employee was using an ac dielectric test set to test a 305-meter length of armored cable (AC-90, Type ACTHH, AWG 12-2). The tests were performed at about 2000 volts. The employee was standing on a non-conductive mat, but had not been provided with rubber insulating gloves. Additionally, the insulation for the test leads was either inadequate or non-existent. Although he had received some on-the-job training from coworkers, the employee had not been trained in electrical safety-related work practices applicable to his job. The employee apparently forgot to turn the voltage setting on the tester to zero before touching the test leads. He was electrocuted when he contacted the energized lead either to remove it or to apply it to the cable while he was touching the metal arm of a cable reel positioned near the test equipment. Exit and entry burns were found on his thumb and index finger, on his left hand, and across his buttocks.
Keywords: E GI V, ELECTRICAL, ELECTRICAL TESTING, ELECTROCUTED, TEST EQUIPMENT, UNGUARDED LIVE PARTS, UNTRAINED
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 2116127 | Fatality | Electric Shock | Inspectors, testers and graders |