Powered by GoogleTranslate

Inspection Detail

Inspection: 1957810 - Whitehead Electric Co.

Inspection Information - Office: Atlanta East Area Office

 

Inspection Nr: 1957810
Report ID: 0418100
Date Opened: 11/14/1984

Site Address:
Whitehead Electric Co.
5395 Roswell Road, N.E.
Atlanta, GA 30342

Mailing Address:
210 14th St., N.W., Atlanta, GA 30318

Union Status: NonUnion

SIC:1731

NAICS: 0 


Inspection Type: Accident

Scope: Complete

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 11/16/1984

Planning Guide: Safety-Construction

Emphasis:

Case Closed: 01/07/1985


Related Activity
Type Activity Nr Safety Health
Accident 360653091
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $490 $0 $0 $0 $0 $490
Current Penalty $245 $0 $0 $0 $0 $245
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001A Serious 19260400 C01 12/10/1984 12/13/1984 $245 $490 $0 I - Informal Settlement  
2. 01001B Serious 19260400 G01 12/10/1984 12/13/1984 $0 $0 $0 -  

Investigation Summary

Investigation Nr: 14541809
Event: 11/08/1984
ELECTRIC SHOCK - DIRECT CONTACT WITH LIVE PARTS

AN ELECTRICIAN HAD REMOVED A TEMPORARY LIGHTING FIXTURE IN AN OCCUPIED OFFICE AND WAS INSTALLING A JUNCTION BOX FOR A PERMANENT FIXTURE. NO LOCKOUT OR TAGGING PROCEDURE WAS BEING USED. HE WAS DEPENDING ON THE WALL SWITCH TO ISOLATE THE CIRCUIT. BETWEEN THE TIME THE TEMPORARY FIXTURE WAS REMOVED AND THE TIME HE STARTED TO WIRE THE BOX, THE WALL SWITCH HAD BEEN TURNED "ON", ENERGIZING THE CIRCUIT. APPARENTLY, HE HELD HE BOX IN ONE HAND AND THE CONDUCTOR IN THE OTHER AS HE INSERTED THE CONDUCTOR INTO THE BOX. BURN MARKS INDICATED THAT CURRENT FROM THE 277-VOLT CIRCUIT FLOWED FROM HAND TO HAND. HE WAS ELECTROCUTED.

Keywords: LIGHTING CIRCUIT, ELECTRICAL, ELECTRICIAN, ELECTROCUTED, ELECTRICAL WORK, LOCKOUT, E C, TAG, ELECTRICAL BOX

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 1957810 Fatality Electric Shock Electricians
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.