Powered by GoogleTranslate

Inspection Detail

Inspection: 1921964 - Liquid Air Corporation

Inspection Information - Office: Baton Rouge Area Office

 

Inspection Nr: 1921964
Report ID: 0625700
Date Opened: 04/24/1985

Site Address:
Liquid Air Corporation
Columbia Southern Road
Lake Charles, LA 70602

Mailing Address:
Po Box 276, Westlake, LA 70669

Union Status: NonUnion

SIC:2813

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 05/08/1985

Planning Guide: Safety-Manufacturing

Emphasis:

Case Closed: 09/30/1986


Related Activity
Type Activity Nr Safety Health
Accident 360550487
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 1 3
Current Violations 1 1
Initial Penalty $840 $0 $0 $0 $0 $840
Current Penalty $0 $0 $0 $0 $0 $0
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19100132 A 05/09/1985 05/12/1985 $420 $420 $0 I - Informal Settlement Citation has been deleted.
2. 01002 Serious 19100303 H02 I 05/09/1985 05/12/1985 $420 $420 $0 I - Informal Settlement Citation has been deleted.
3. 02001 Other 19040008 05/09/1985 05/12/1985 $0 $0 $0 -  

Investigation Summary

Investigation Nr: 14392997
Event: 04/20/1985
ELECTRIC SHOCK - CONTACT WITH ENERGIZED PARTS

Two employees were replacing a fuse in a 4160-volt starter (switchgear) for an air compressor. The switchgear was supplied with an interlock requiring a lever to be pulled down to disengage the contactor unit from the bus. The interlock was designed to prevent the cabinet door from opening when the contactor unit is engaged. It was also designed to prevent the cart to be racked in when the cabinet door is open. The interlock was broken, and one of the employees was pushing on the cart while the other employee was jiggling the lever to align the cart so it could be racked in. The cart contacted the 4160-volt bus, electrocuting the employee pushing on it.

Keywords: E GI V, ELECTRICAL, ELECTRICIAN, ELECTROCUTED, ELECTRICAL WORK, INTERLOCK, LOCKOUT, SWITCHGEAR, MECH MALFUNCTION

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 1921964 Fatality Electric Shock Electricians
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close