Inspection: 18871947 - Baltimore Thermal Energy Corp.

Inspection Information - Office: Department Of Labor, Licensing, And Regulation Division Of Labor And Industry Maryland Occupational Safety And Health

 

Inspection Nr: 18871947
Report ID: 0352420
Date Opened: 07/27/1987

Site Address:
Baltimore Thermal Energy Corp.
100 E. Pratt Street
Baltimore, MD 21202

Mailing Address:
1400 Ridgeley Street, Baltimore, MD 21230

Union Status: NonUnion

SIC:4961

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 10/20/1987

Emphasis:

Case Closed: 01/06/1988


Related Activity
Type Activity Nr Safety Health
Accident 360750871
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 3 3
Current Violations 3 3
Initial Penalty $1,360 $0 $0 $0 $0 $1,360
Current Penalty $890 $0 $0 $0 $0 $890
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citation Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 09123503 A 5 A 11/19/1987 11/22/1987 $420 $420 $0 -  
2. 02001 Serious 09123503 A 5 B 11/19/1987 11/22/1987 $0 $470 $0 I - Informal Settlement  
3. 03001 Serious 19100132 A 11/19/1987 11/22/1987 $470 $470 $0 -  

Investigation Summary

Investigation Nr: 825505
Event: 07/24/1987
EMPLOYEE KILLED WHEN STEAM LINE RUPTURED

AT APPROXIMATELY 11:30 PM ON JULY 24, 1987, A 4 INCH DIAMETER STRAINER RUPTURED CAUSING A HIGH PRESSURE STEAM LEAK. THE STRAINER WAS PART OF A STEAM PIPELINE WHICH ENTERS THE BOILER ROOM OF THE I.B.M. BUILDING. THE STEAM LEAK WAS LOCATED IN AN UNDERGROUND VAULT, WHICH IS CONNECTED TO A TUNNEL LEADING INTO THE BOILER ROOM OF THE I.B.M. BUILDING. THE VAULT HAS A REMOVABLE METAL GRATE TOP FROM WHICH A WORK LADDER IS USED TO GAIN ACCESS INTO THE VAULT. THE NIGHT CREW HAD REPLACED THE RUPTURED STRAINER WITH A NEW ONE. IN THE EARLY MORNING HOURS OF THE NEXT DAY (7/25), SEVERAL EMPLOYEES HAD TROUBLE ADJUSTING THE REGULATOR PILOT VALVES. THE PILOT VALVES CONTROL THE STEAM PRESSURE FLOW INTO THE I.B.M. BUILDING. THAT MORNING AT ABOUT 6 AM, EMPLOYEE #1 WAS CALLED IN TO TAKE OVER THE ADJUSTMENTS OF THE PILOT VALVES. FROM 6:45 TO 9 AM HE WAS WORKING BY HIMSELF. AT APPROXIMATELY 9 AM THE 4 INCH STRAINER RUPTURED AGAIN. HE HURRIED INTO THE TUNNEL TRYING TO ESCAPE THE STEAM. HE DID NOT MAKE IT TO SAFETY. HIS BODY WAS FOUND IN THE TUNNEL ABOUT 30 FEET FROM THE DOORWAY LEADING INTO THE BOILER ROOM. THE VAULT WAS 16 FEET, 8 INCHES LONG, 8 FEET WIDE AND 8 FEET, 11 INCHES HIGH. THE TUNNEL WAS 223 FEET, 7 INCHES LONG, 6 FEET, 10 INCHES WIDE AND 10 FEET HIGH.

Keywords: STEAM LINE, TUNNEL, ELECTRICAL VAULT, CONFINED SPACE, WORK RULES, BOILER, RUPTURE, STEAM, PIPELINE

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 18871947 Fatality Burn/Scald(Heat) Plumbers, pipefitters and steamfitters
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.