Inspection Detail
Inspection: 18860536 - Ennis Electrico Co, Inc.
Inspection Information - Office: Department Of Labor, Licensing, And Regulation Division Of Labor And Industry Maryland Occupational Safety And Health
Site Address: 
			   Ennis Electrico Co, Inc.
			   Building #41, N I H
Bethesda, MD 20814
Mailing Address: 
			   10406 Balls Ford Rd, Manassas, VA 22110
Union Status: NonUnion
SIC:1731
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 09/08/1987
Planning Guide: Safety-Construction
Emphasis:
Case Closed: 09/21/1987
| Type | Activity Nr | Safety | Health | 
|---|---|---|---|
| Accident | 360751960 | 
Investigation Summary
A supervisory electrician and his apprentice had just installed new conduit leading to a carbon dioxide tank. The supervisor and a building engineer thought they had deenergized the circuit by opening a circuit breaker. However, the labeling was in pencil; and they had opened and tagged only one of the two circuit breakers protecting the carbon dioxide unit. (A 15-ampere circuit breaker was opened, but a 50-ampere circuit breaker was never located.) The supervisor hooked a metal fish tape that was in the conduit to 480-volt, three-phase No. 8 conductors that were still energized. When the fish tape contacted the conductors, the supervisor was electrocuted. His employer had instituted a rule requiring employees to check wiring for voltage to assure that circuits are deenergized. The supervisor had apparently failed to follow this rule.
Keywords: METAL WIRE, E GI IV, ELECTRICAL, ELECTRICIAN, ELECTROCUTED, ELECTRICAL WORK, LOCKOUT, ELECTRIC CONDUCTOR
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation | 
|---|---|---|---|---|---|---|
| 1 | 18860536 | Fatality | Electric Shock | Supervisors; electricians & power transm. install. | 
 Translate