Inspection Detail
Inspection: 18542670 - Mccall Brothers, Inc.
Inspection Information - Office: Nc Department Of Labor - Raleigh
Site Address:
Mccall Brothers, Inc.
11600 Block Of Plaza Road Ext.
Charlotte, NC 28215
Mailing Address:
6700 Belhaven Blvd., Charlotte, NC 28214
Union Status: NonUnion
SIC:1781
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 10/06/1988
Emphasis:
Case Closed: 04/03/1989
Type | Activity Nr | Safety | Health |
---|---|---|---|
Accident | 360260236 |
Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
---|---|---|---|---|---|---|
Initial Violations | 1 | 1 | ||||
Current Violations | 1 | 1 | ||||
Initial Penalty | $400 | $0 | $0 | $0 | $0 | $400 |
Current Penalty | $400 | $0 | $0 | $0 | $0 | $400 |
FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
# | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
---|---|---|---|---|---|---|---|---|---|---|---|
1. | 01001A | Serious | 19260404 F09 | 01/30/1989 | 03/04/1989 | $400 | $400 | $0 | - | ||
2. | 01001B | Serious | 19260404 F10 | 01/30/1989 | 03/04/1989 | $0 | $0 | $0 | - | ||
3. | 01001C | Serious | 19260405 E01 | 01/30/1989 | 03/04/1989 | $0 | $0 | $0 | - |
Investigation Summary
AN EMPLOYEE WAS TOUCHING A THE METAL FRAME OF A PORTABLE GENERATOR. AN ABRADED CONDUCTOR INSIDE A PANEL WAS FAULTED TO THE GENERATOR'S FRAME. THE GROUNDING ELECTRODE AND BONDING CONDUCTOR WERE INEFFECTIVE, ALLOWING THE FRAME OF THE GENERATOR TO BECOME ENERGIZED AT A LOW VOLTAGE. THE EMPLOYEE, WHO WAS STANDING ON WET GROUND, WAS ELECTROCUTED.
Keywords: ELECTRICAL, ELECTROCUTED, E C, GROUND FAULT, BONDING, ELECTRIC CONDUCTOR, SYSTEM GROUNDING, ELECTRIC GENERATOR
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 18542670 | Fatality | Electric Shock | Drillers, earth |