Powered by GoogleTranslate

Inspection Detail

Inspection: 18535104 - Watson Electrical Construction Co.

Inspection Information - Office: Nc Department Of Labor - Raleigh

 

Inspection Nr: 18535104
Report ID: 0453710
Date Opened: 08/23/1988

Site Address:
Watson Electrical Construction Co.
Square D Plant, Us 64 East
Knightdale, NC 27545

Mailing Address:
Post Office Box 3105, Wilson, NC 27893

Union Status: NonUnion

SIC:1731

NAICS: 0 


Inspection Type: Accident

Scope: Complete

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 08/23/1988

Emphasis:

Case Closed: 02/16/1989


Related Activity
Type Activity Nr Safety Health
Accident 360263487
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $0 $0 $0 $0 $0 $0
Current Penalty $0 $0 $0 $0 $0 $0
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other 19260500 E01 III 01/26/1989 02/01/1989 $0 $0 $0 -  

Investigation Summary

Investigation Nr: 809525
Event: 08/19/1988
BURN - FAULT IN SWITCHGEAR CABINET

AN ELECTRICIAN WAS BOLTING A NEW 4160-VOLT SWITCHGEAR CABINET TO AN EXISTING 4160-VOLT SWITCHGEAR CABINET. THE NEW CABINET HAD NOT YET BEEN ENERGIZED, BUT THE EXISTING CABINET REMAINED ENERGIZED. THE ELECTRICIAN WAS STANDING ON TWO RUBBER MATS AS HE WAS WORKING. HE WAS INSTALLING THE LAST BOLT AT THE BOTTOM OF THE CABINETS WHEN HE LOST HIS BALANCE AND FELL INTO THE EXISTING CABINET. THE BOX END WRENCH IN THE EMPLOYEE'S RIGHT HAND CONTACTED ONE OF THE ENERGIZED PHASE CONDUCTORS INSIDE THE CABINET AND THE GROUNDED FRAME OF THE CABINET. THE RESULTING ELECTRIC ARC CAUSED SEVERE BURNS TO THE EMPLOYEE'S RIGHT HAND, FACE, AND NECK. THE EMPLOYEE WAS HOSPITALIZED FOR HIS INJURIES.

Keywords: BURN, E GI II, ELEC PROTECT EQUIP, ELECTRIC ARC, ELECTRICAL, ELECTRICIAN, ELECTRICAL WORK, LOCKOUT, ELECTRICAL FAULT, SWITCHGEAR

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 18535104 Hospitalized injury Burn/Scald(Heat) Supervisors; electricians & power transm. install.
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.