Powered by GoogleTranslate

Inspection Detail

Inspection: 18518688 - Federal Paper Board Co., Inc.

Inspection Information - Office: Nc Department Of Labor - Raleigh

 

Inspection Nr: 18518688
Report ID: 0453710
Date Opened: 01/02/1992

Site Address:
Federal Paper Board Co., Inc.
John L. Riegel Rd.
Riegelwood, NC 28456

Mailing Address:
P. O. Box 8, Riegelwood, NC 28456

Union Status: Union

SIC:2621

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 01/08/1992

Planning Guide: Safety-Manufacturing

Emphasis:

Case Closed: 08/14/1994


Related Activity
Type Activity Nr Safety Health
Accident 360489926
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 2 3
Current Violations 3 3
Initial Penalty $7,000 $140,000 $0 $0 $0 $147,000
Current Penalty $7,500 $0 $0 $0 $0 $7,500
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19100261 B04 04/24/1992 04/30/1992 $2,500 $70,000 $0 05/11/1992 F - Formal Settlement  
2. 01002 Serious 19100261 B05 04/24/1992 04/30/1992 $2,500 $70,000 $0 05/11/1992 F - Formal Settlement  
3. 02001 Serious 95012901 04/24/1992 04/30/1992 $2,500 $7,000 $0 05/11/1992 F - Formal Settlement  

Investigation Summary

Investigation Nr: 170063374
Event: 12/31/1991
ELECTRIC SHOCK - DIRECT CONTACT WITH ENERGIZED PARTS

THREE EMPLOYEES, AN ELECTRICIAN, A RECOVERY FOREMAN, AND AN INSTRUMENT MECHANIC, WERE ASSIGNED TO WORK ON A RECOVERY BOILER PRECIPITATOR AT A PULP AND PAPER MILL. THE PRECIPITATOR HAD A GROUNDING PROBLEM IN THE THIRD FIELD OF THE PENTHOUSE AREA. THE INSTRUMENT MECHANIC RAN A GAS TEST FOR OXYGEN, HYDROGEN SULFIDE, FLAMMABILITY, AND MERCAPTANS. THE TEST RESULTS WERE NEGATIVE, AND A CONFINED SPACE PERMIT WAS ISSUED. HOWEVER, EVEN THOUGH THE RECOVERY FOREMAN HAD AUTHORIZED THE PERMIT, THE PRECIPITATOR HAD NOT BEEN DEENERGIZED AND LOCKED OUT. THE ELECTRICIAN ENTERED THE CONFINED SPACE AND WAS ELECTROCUTED WHEN HE APPARENTLY CONTACTED AN EXPOSED ENERGIZED PART OF THE 51-KILOVOLT DC PRECIPITATOR.

Keywords: E GI IV, ELECTRICAL, CONFINED SPACE, ELECTRICIAN, ELECTROCUTED, ELECTRICAL WORK, LOCKOUT, ELEC CIRC PART--MISC, ELEC EQUIPMENT--MISC

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 18518688 Fatality Electric Shock Electricians
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.