Inspection Detail
Inspection: 18512541 - Line Construction Co., Inc.
Inspection Information - Office: Nc Department Of Labor - Raleigh
Site Address:
Line Construction Co., Inc.
Rt. 1, Sifford Rd.
Lowesville, NC 28164
Mailing Address:
P. O. Box 3937, Sanford, NC 27331
Union Status: NonUnion
SIC:1623
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 09/28/1989
Emphasis:
Case Closed: 11/14/1989
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 360487599 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 2 | 2 | ||||
| Current Violations | 2 | 2 | ||||
| Initial Penalty | $700 | $0 | $0 | $0 | $0 | $700 |
| Current Penalty | $700 | $0 | $0 | $0 | $0 | $700 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Serious | 19260021 B02 | 10/25/1989 | 10/31/1989 | $350 | $350 | $0 | - | ||
| 2. | 01002A | Serious | 19260955 C03 | 10/25/1989 | 10/31/1989 | $350 | $350 | $0 | - | ||
| 3. | 01002B | Serious | 19260955 C04 I | 10/25/1989 | 10/31/1989 | $0 | $0 | $0 | - |
Investigation Summary
A POWER LINE CREW WAS RELOCATING AN OVERHEAD POWER LINE THAT HAD FALLEN TO THE GROUND DURING A STORM. THEY CUT A JUMPER WIRE TO DEENERGIZE THE LINE AND TAPED IT TO THE CONDUCTOR. AS THE EMPLOYEES WERE MOVING THE LINE, THE JUMPER CAME LOOSE AND CONTACTED AN ENERGIZED 7200-VOLT OVERHEAD POWER LINE. BOTH EMPLOYEES RECEIVED ELECTRIC SHOCKS AND WERE ADMITTED TO A HOSPITAL FOR TREATMENT. ONE OF THEM DIED 4 DAYS LATER. THE OTHER WAS TREATED FOR HIS INJURIES AND RELEASED 2 DAYS AFTER THE ACCIDENT.
Keywords: OVERHEAD POWER LINE, PROTECTIVE GROUNDING, ELECTRICAL, POWER LINE WORKER, ELECTROCUTED, E PTD, ELEC UTILITY WORK, ELECTRIC CONDUCTOR, ELECTRIC SHOCK
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 18512541 | Fatality | Electric Shock | Electrical power installers and repairers | ||
| 2 | 18512541 | Hospitalized injury | Electric Shock | Supervisors; electricians & power transm. install. |