Powered by GoogleTranslate

Inspection Detail

Inspection: 18344853 - Georgia Power Company

Inspection Information - Office: Atlanta East Area Office

 

Inspection Nr: 18344853
Report ID: 0418100
Date Opened: 10/11/1989

Site Address:
Georgia Power Company
Buena Vista Road At Andrews Drive
Columbus, GA 31907

Mailing Address:
3610 Gentain Blvd., Columbus, GA 31907

Union Status: Union

SIC:4911

NAICS: 0 


Inspection Type: Accident

Scope: Complete

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 10/12/1989

Planning Guide: Safety-Construction

Emphasis:

Case Closed: 08/07/1990


Related Activity
Type Activity Nr Safety Health
Accident 360414262
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 2
Current Violations 2 2
Initial Penalty $1,280 $0 $0 $0 $0 $1,280
Current Penalty $640 $0 $0 $0 $0 $640
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19260416 A01 12/11/1989 12/14/1989 $320 $640 $0 01/09/1990 F - Formal Settlement  
2. 01002 Serious 19260954 F 12/11/1989 12/14/1989 $320 $640 $0 01/09/1990 F - Formal Settlement  

Investigation Summary

Investigation Nr: 608406
Event: 10/06/1989
ELECTRIC SHOCK - CONTACT WITH OVERHEAD LINE THRU CONDUCTOR

AN ELECTRIC UTILITY CREW WAS INSTALLING A NEW POWER LINE FOR A CONVENIENCE STORE. TWO MEMBERS OF THE CREW WERE IN AERIAL LIFTS AT THE LAST OF THREE NEW POLES, AT THE FAR END FROM THE STORE. ANOTHER POWER LINE WORKER WAS CLIMBING THE MIDDLE POLE, WHICH WAS 105 FEET AWAY. THE TWO EMPLOYEES IN THE AERIAL LIFTS ASKED THE THIRD EMPLOYEE IF HE WANTED THEM TO GROUND THE NEW LINE. THE EMPLOYEE ON THE POLE RESPONDED THAT GROUNDING WAS NOT NEEDED SINCE HE WOULD WEAR HIS RUBBER GLOVES. THE GROUND MAN, WHO WAS AT THE BOTTOM OF THE MIDDLE POLE, PASSED ARMOR RODS TO THE EMPLOYEE ON THE POLE, SO THAT THE POWER LINE WORKER COULD ATTACH THE CONDUCTOR TO THE POLE AND REMOVE THE ROLLER BLOCK. THE CONDUCTORS HAD BEEN PULLED BACK AND TAPED AT THE FIRST POLE (THE ONE NEAREST TO THE STORE), WHICH WAS 150 FEET AWAY FROM THE MIDDLE POLE. ONE OF THE CONDUCTORS PULLED AWAY FROM THE TAPE, FLIPPED AROUND, AND CONTACTED A 7200-VOLT OVERHEAD POWER LINE. THE POWER LINE WORKER ON THE POLE, WHO WAS IN CONTACT WITH THIS CONDUCTOR, WAS ELECTROCUTED.

Keywords: ELEC PROTECT EQUIP, OVERHEAD POWER LINE, ELECTRICAL, POWER LINE WORKER, ELECTROCUTED, E PTD, ELEC UTILITY WORK, ELECTRIC CONDUCTOR

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 18344853 Fatality Electric Shock Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.