Inspection Detail
Inspection: 18318048 - The Bibb Company
Inspection Information - Office: Atlanta East Area Office
Site Address:
The Bibb Company
1 Osmundy Street
Porterdale, GA 30270
Mailing Address:
P.O. Box 595, Porterdale, GA 30270
Union Status: NonUnion
SIC:2281
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 11/06/1989
Planning Guide: Safety-Manufacturing
Emphasis:
Case Closed: 12/21/1989
Type | Activity Nr | Safety | Health |
---|---|---|---|
Accident | 360414031 |
Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
---|---|---|---|---|---|---|
Initial Violations | 2 | 2 | ||||
Current Violations | 2 | 2 | ||||
Initial Penalty | $1,400 | $0 | $0 | $0 | $0 | $1,400 |
Current Penalty | $1,400 | $0 | $0 | $0 | $0 | $1,400 |
FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
# | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
---|---|---|---|---|---|---|---|---|---|---|---|
1. | 01001 | Serious | 19100184 E02 I | 12/01/1989 | 12/14/1989 | $400 | $400 | $0 | - | ||
2. | 01002A | Serious | 19100303 G02 I | 12/01/1989 | 12/04/1989 | $1,000 | $1,000 | $0 | - | ||
3. | 01002B | Serious | 19100304 F04 | 12/01/1989 | 12/04/1989 | $0 | $0 | $0 | - |
Investigation Summary
AN 18-YEAR OLD EMPLOYEE COLLAPSED DEAD ON THE JOB. HE HAD BEEN SEEN, JUST BEFORE HIS COLLAPSE, PULLING A REEL-TYPE MONORAIL HOIST BY ITS HOOK. UPON INSPECTION OF THE HOIST, ITS EQUIPMENT GROUNDING CONDUCTOR WAS FOUND NOT TO HAVE BEEN CONNECTED TO ITS TERMINAL, AND A METAL CLAMP USED TO SECURE THE REEL CABLE TO THE HOIST MOTOR WAS FOUND TO HAVE CUT THROUGH THE OUTER JACKET OF THE CABLE AND THROUGH THE INSULATION ON THE BLACK CONDUCTOR. THE CLAMP WAS ALSO FOUND TO BE IN CONTACT WITH THE EXPOSED PORTION OF THE CIRCUIT CONDUCTOR. THUS, AT THE TIME OF THE INCIDENT, THE FRAME OF THE HOIST WAS ENERGIZED. THE AUTOPSY PERFORMED ON THE DECEASED EMPLOYEE FOUND NO BURN MARKS AS EVIDENCE OF ELECTROCUTION, BUT DID FIND A PRE-EXISTING HEART CONDITION. AS A RESULT, THE AUTOPSY REPORT STATED THAT THE CAUSE OF DEATH "COULD NOT BE ABSOLUTELY DETERMINED."
Keywords: ELECTRICAL, ELECTRIC CABLE, E GI VII, ELECTROCUTED, GROUND FAULT, EQUIPMENT GROUNDING, ELEC EQUIPMENT--MISC
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 18318048 | Fatality | Electric Shock | Occupation not reported |