Powered by GoogleTranslate

Inspection Detail

Inspection: 18315564 - Southwire - Cds

Inspection Information - Office: Atlanta East Area Office

 

Inspection Nr: 18315564
Report ID: 0418100
Date Opened: 02/23/1989

Site Address:
Southwire - Cds
Central Road
Carrollton, GA 30117

Mailing Address:
P.O. Box 1000, Carrollton, GA 30119

Union Status: NonUnion

SIC:3341

NAICS: 0 


Inspection Type: Referral

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 02/28/1989

Planning Guide: Safety-Manufacturing

Emphasis:

Case Closed: 05/16/1989


Related Activity
Type Activity Nr Safety Health
Referral 901017418 Yes
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 2
Current Violations 2 2
Initial Penalty $1,280 $0 $0 $0 $0 $1,280
Current Penalty $1,280 $0 $0 $0 $0 $1,280
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 5A0001 03/13/1989 04/13/1989 $640 $640 $0 I - Informal Settlement  
2. 01002 Serious 19101200 H02 III 03/13/1989 04/13/1989 $640 $640 $0 I - Informal Settlement  

Investigation Summary

Investigation Nr: 14336283
Event: 02/23/1989
Employees burned during flash fire

Employees #1 and #2, maintenance workers, were cleaning a Y-strainer on a natural gas line for furnaces in a secondary copper smelter. The main natural gas line valve was closed. The furnaces have a back-up system that uses propane. The propane valve closest to Employees #1 and #2 was open. Another employee opened the main propane valve to switch the system over from natural gas to propane. The propane gas then seeped back through the open valve into the area in which the employees were working. It ignited, causing a flash fire. Employee #1 was seriously burned; Employee #2 was also burned, but not as severely as Employee #1. None of the valves was locked out or tagged out.

Keywords: BURN, LEAK, MAINTENANCE, WORK RULES, CLEANING, FIRE, NATURAL GAS, LOCKOUT, VALVE, PROPANE

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 18315564 Hospitalized injury Burn/Scald(Heat) Occupation not reported
2 18315564 Hospitalized injury Burn/Scald(Heat) Occupation not reported
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.