Powered by GoogleTranslate

Inspection Detail

Inspection: 18313726 - Croft - Mullins Electric Co., Inc.

Inspection Information - Office: Atlanta East Area Office

 

Inspection Nr: 18313726
Report ID: 0418100
Date Opened: 12/29/1988

Site Address:
Croft - Mullins Electric Co., Inc.
Robins Afb F Street, Bldg 351
Warner Robins, GA 31088

Mailing Address:
P.O. Box 4124, Macon, GA 31208

Union Status: NonUnion

SIC:1623

NAICS: 0 


Inspection Type: Referral

Scope: Partial

Advanced Notice: Y

Ownership: Private

Safety/Health: Safety

Close Conference: 01/12/1989

Planning Guide: Safety-Construction

Emphasis:

Case Closed: 02/23/1990


Related Activity
Type Activity Nr Safety Health
Referral 901180307 Yes
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 3 3
Current Violations 2 2
Initial Penalty $840 $0 $0 $0 $0 $840
Current Penalty $420 $0 $0 $0 $0 $420
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citation Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19260021 B02 01/17/1989 01/27/1989 $140 $280 $0 02/08/1989 F - Formal Settlement  
2. 01002 Serious 19260556 B02 V 01/17/1989 01/20/1989 $280 $280 $0 -  
3. 01003 Serious 19260950 C01 I 01/17/1989 01/20/1989 $280 $280 $0 02/08/1989 F - Formal Settlement Citation has been deleted.

Investigation Summary

Investigation Nr: 14336218
Event: 12/27/1988
ELECTRIC SHOCK - DIRECT CONTACT WITH OVERHEAD LINE

A POWER LINE WORKER WAS PULLING AN UNDERGROUND CABLE AND WAS TO INSTALL IT UP AN EXISTING UTILITY POLE. THE EMPLOYEE HAD USED CLASS 2 RUBBER INSULATING GLOVES WHILE HE WAS WORKING EARLIER IN THE DAY TO SET UP A ROPE AND PULLEY ON THE UTILITY POLE. AS THE EMPLOYEE WAS WORKING AT GROUND LEVEL, THE PULLEY TURNED AND THE ROPE STARTED RUBBING AGAINST THE METAL UTILITY POLE. THE EMPLOYEE TURNED OFF THE WINCH AND GOT INTO AN AERIAL LIFT BUCKET TO STRAIGHTEN THE PULLEY. HE PUT HIS RUBBER GLOVES ON THE HOOKS IN THE BUCKET, BUT HE DID NOT DON THEM WHEN HE GOT INTO THE ENERGIZED AREA. WHEN THE BUCKET GOT TO THE LEVEL OF THE PULLEY, THE EMPLOYEE REACHED ACROSS A 7200-VOLT OVERHEAD POWER LINE AND CONTACTED THE POLE. THE EMPLOYEE RECEIVED AN ELECTRIC SHOCK AND LOST CONSCIOUSNESS. OTHER EMPLOYEES AT THE SCENE MOVED THE BUCKET TO GET THE INJURED EMPLOYEE OFF THE POWER LINE. THE EMPLOYEE DIED OF HIS INJURIES 11 DAYS LATER.

Keywords: ELEC PROTECT EQUIP, OVERHEAD POWER LINE, ELECTRICAL, POWER LINE WORKER, ELECTROCUTED, E PTD, ELEC UTILITY WORK, AERIAL LIFT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 18313726 Fatality Electric Shock Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.