Inspection: 18305615 - Frank Laird Construction Company

Inspection Information - Office: Jackson Area Office

 

Inspection Nr: 18305615
Report ID: 0419400
Date Opened: 10/16/1991

Site Address:
Frank Laird Construction Company
12 Miles East On Hwy 48
Magnolia, MS 39652

Mailing Address:
Rt. 2. Box 157 A, Mccall Creek, MS 39647

Union Status: NonUnion

SIC:1623

NAICS: 0 


Inspection Type: Accident

Scope: Complete

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 10/18/1991

Planning Guide: Safety-Construction

Emphasis:

Case Closed: 02/24/1992


Related Activity
Type Activity Nr Safety Health
Accident 360799175
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 1 3
Current Violations 2 1 3
Initial Penalty $6,500 $0 $0 $0 $0 $6,500
Current Penalty $2,000 $0 $0 $0 $0 $2,000
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19260955 A05 I 11/19/1991 11/29/1991 $1,000 $5,000 $0 I - Informal Settlement  
2. 01002 Serious 19260955 A06 I 11/19/1991 11/29/1991 $1,000 $1,500 $0 I - Informal Settlement  
3. 02001 Other 19260021 B02 11/19/1991 11/29/1991 $0 $0 $0 -  

Investigation Summary

Investigation Nr: 603126
Event: 10/15/1991
ELECTRIC SHOCK - CONTACT WITH OVERHEAD LINE THRU POWER POLE

TWO EMPLOYEES WERE REPLACING ROTTEN AND DAMAGED UTILITY POLES. TO DO THIS, THE EMPLOYEES DUG A NEW HOLE NEXT TO THE EXISTING POLE, SET THE NEW POLE, AND THEN TRANSFERRED THE TWO CONDUCTORS TO IT. (THIS WORK WAS PERFORMED WITH THE 7620-VOLT OVERHEAD POWER LINE ENERGIZED.) A NEW POLE WAS LIFTED, AND ONE OF THE EMPLOYEES WAS GUIDING THE BASE OF THE POLE INTO ITS HOLE. THE LINE INSULATORS, GUY, AND POLE GROUND HAD ALREADY BEEN INSTALLED ON THE POLE. THE POLE GROUND WAS ATTACHED TO THE LOWER, NEUTRAL INSULATOR MOUNTING BOLT AND RAN THE LENGTH OF THE POLE TO WITHIN ABOUT 6 FEET OF ITS BASE. THE HYDRAULIC CRANE THE EMPLOYEES WERE USING HAD THE POLE LIFTED TO AN ALMOST VERTICAL POSITION WHEN THE LOWER INSULATOR MOUNTING BOLT CONTACTED THE POWER LINE. THE EMPLOYEE GUIDING THE BASE OF THE POLE, WHO WAS NOT WEARING RUBBER INSULATING GLOVES, WAS ELECTROCUTED.

Keywords: ELEC PROTECT EQUIP, OVERHEAD POWER LINE, ELECTRICAL, POWER LINE WORKER, ELECTROCUTED, E PTD, GUY, ELEC UTILITY WORK, UTILITY POLE

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 18305615 Fatality Electric Shock Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.