Powered by GoogleTranslate

Inspection Detail

Inspection: 17742982 - Apollo Steel Corporation

Inspection Information - Office: Buffalo Area Office

 

Inspection Nr: 17742982
Report ID: 0213600
Date Opened: 10/13/1988

Site Address:
Apollo Steel Corporation
4511 Hyde Park Blvd.
Niagara Falls, NY 14305

Mailing Address:
4800 Wilton Ave., Niagara Falls, NY 14304

Union Status: Union

SIC:1791

NAICS: 0 


Inspection Type: Referral

Scope: Complete

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 10/27/1988

Planning Guide: Safety-Construction

Emphasis:

Case Closed: 11/21/1988


Related Activity
Type Activity Nr Safety Health
Referral 901190777 Yes
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 2
Current Violations 2 2
Initial Penalty $1,260 $0 $0 $0 $0 $1,260
Current Penalty $630 $0 $0 $0 $0 $630
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19260416 A01 11/02/1988 11/05/1988 $315 $630 $0 I - Informal Settlement  
2. 01002A Serious 19260416 A03 11/02/1988 11/05/1988 $315 $630 $0 I - Informal Settlement  
3. 01002B Serious 19260416 A03 11/02/1988 11/05/1988 $0 $0 $0 -  
4. 01002C Serious 19260416 A03 11/02/1988 11/05/1988 $0 $0 $0 -  

Investigation Summary

Investigation Nr: 14485296
Event: 10/06/1988
ELECTRIC SHOCK - DIRECT CONTACT WITH ENERGIZED PARTS

AN EMPLOYEE ENTERED AN UNLOCKED TRANSFORMER ROOM TO ASCERTAIN IF THE BUS PASSING THROUGH THE ROOM'S WALL WAS CONNECTED TO THE TRANSFORMER. THE CABLES HOLDING THIS BUS WERE TO BE CUT WITH A TORCH. AFTER SURVEYING THE AREA AND DETERMINING THAT THE BOLT WAS MISSING FROM THE BUS AND THAT THE POWER TO THE TRANSFORMER WAS DEENERGIZED, THE EMPLOYEE CLIMBED ATOP THE TRANSFORMER TO GET A CLOSER LOOK AT THE BUS. THE EMPLOYEE CONTACTED AN ENERGIZED 12-KILOVOLT FUSE. THE CURRENT ENTRY AND EXIT POINTS WERE THE EMPLOYEE'S RIGHT ARM IN THE TRICEPS AREA AND THE LEFT FOREARM, WHERE THE CURRENT LEFT A HOLE IN HIS ARM. THE EMPLOYEE WAS HOSPITALIZED FOR HIS INJURIES FOR A TOTAL OF 4 DAYS.

Keywords: BURN, FUSE, ELEC PROTECT EQUIP, E GI IV, ELECTRICAL, LOCKOUT, ELECTRIC SHOCK, TRANSFORMER

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 17742982 Hospitalized injury Electric Shock Occupation not reported
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.