Inspection Detail
Inspection: 17721374 - Consolidated Petroleum Terminal, Inc.
Inspection Information - Office: Long Island Area Office
Site Address:
Consolidated Petroleum Terminal, Inc.
Terminal/Bellmeade Road
East Setauket, NY 11733
Mailing Address:
, , 00000
Union Status: Union
SIC:5171
NAICS: 0
Inspection Type: Referral
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 10/22/1987
Emphasis:
Case Closed: 02/08/1988
Type | Activity Nr | Safety | Health |
---|---|---|---|
Referral | 900838012 | Yes |
Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
---|---|---|---|---|---|---|
Initial Violations | 1 | 1 | ||||
Current Violations | 1 | 1 | ||||
Initial Penalty | $0 | $0 | $2,000 | $0 | $0 | $2,000 |
Current Penalty | $0 | $0 | $2,000 | $0 | $0 | $2,000 |
FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
# | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
---|---|---|---|---|---|---|---|---|---|---|---|
1. | 01001 | Repeat | 19100307 B | 12/08/1987 | 12/14/1987 | $2,000 | $2,000 | $0 | - |
Investigation Summary
AN EMPLOYEE WAS FILLING THE REFRIGERANT SECTION OF A GASOLINE VAPOR CONDENSATION SYSTEM WITH METHYLENE CHLORIDE. HE WAS USING A DAYTON 0.33-HORSEPOWER NON-EXPLOSION-PROOF MOTOR/PUMP, ATTACHED TO ITS SOURCE OF SUPPLY THROUGH A NON-EXPLOSION-PROOF-TYPE EXTENSION CORD SET. THE CORD SET WAS PLUGGED INTO AN ADAPTER CORD SET THAT HAD AN EXPLOSION-PROOF ATTACHMENT PLUG ON ONE END AND A NON-EXPLOSION-PROOF CONNECTOR ON THE OTHER END. THE EMPLOYEE WAS PUMPING THE METHYLENE CHLORIDE FROM 55-GALLON DRUMS IN THE BUCKET OF A BACKHOE. THE EMPLOYEE PLUGGED THE ADAPTER CORD SET, WHICH WAS 3 FEET LONG, INTO AN EXPLOSION-PROOF RECEPTACLE OUTLET ABOUT 100 FEET FROM WHERE HE WAS WORKING. HE THEN RAN THE EXTENSION CORD SET TO THE VAPOR RECOVERY UNIT. HE WAS STARTING HIS SEVENTH DRUM; AND, WHEN HE PLUGGED THE MOTOR'S POWER CORD INTO THE CONNECTOR ON THE CORD SET IN THE GASOLINE-ENRICHED ATMOSPHERE, THERE WAS AN EXPLOSION. THE EMPLOYEE SUSTAINED THIRD DEGREE BURNS OVER 40 PERCENT OF HIS BODY.
Keywords: E GI V, ELECTRICAL, METHYLENE CHLORIDE, CORD SET, ATTACHMENT PLUG, ELECTRIC PUMP, EXPLOSION, CORD CONNECTOR, GASOLINE, EQUIPMENT APPROVAL
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 17721374 | Hospitalized injury | Burn/Scald(Heat) | Occupation not reported |