Powered by GoogleTranslate

Inspection Detail

Case Status: CLOSED

Inspection: 1751755.015 - P&S Electric Llc

Inspection Information - Office: Va-E-Verona (Field Office) - Safety 0355116

 

Inspection Nr: 1751755.015
Report ID: 0355116
Date Opened: 05/28/2024

Site Address:
P&S Electric Llc
153 Sugar Loaf Rd
Staunton, VA 24401

Mailing Address:
409 Calf Mountain Rd, Waynesboro, VA 22980

Union Status: NonUnion

SIC:

NAICS: 238210/Electrical Contractors


Inspection Type: Fat/Cat

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 05/28/2024

Emphasis: N:Fall, S:Fri

Case Closed: 01/16/2025


Related Activity
Type Activity Nr Safety Health
Accident 2167917
Case Status: CLOSED
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 2 3
Current Violations 1 2 3
Initial Penalty $15,375 $0 $0 $0 $0 $15,375
Current Penalty $15,375 $0 $0 $0 $0 $15,375
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19100067 C02 V 11/18/2024 01/13/2025 $15,375 $15,375 $0 P - Petition to Mod Abatement  
2. 02001 Other 19100132 D02 11/18/2024 01/13/2025 $0 $0 $0 P - Petition to Mod Abatement  
3. 02002 Other 19100151 B 11/18/2024 01/13/2025 $0 $0 $0 P - Petition to Mod Abatement  

Investigation Summary

Investigation Nr: 167018.015
Event: 05/24/2024
Employee falls from bucket and strikes truck, new pole, and

At 10:50 a.m. on May 24, 2024, Employee #1 was removing a deteriorated residential electrical service pole in preparation for replacement. After removing the top part of the pole, the employee drove a grounding rod into the remaining pole stump and attached a clamp and strap to both the pole and the rod. The other end of the strap was connected to the aerial lift boom of a bucket truck, with the employee in the bucket. The bucket was used to pull the stump from the ground. After about two hours of work, the stump became free suddenly, causing the boom to recoil with force. The employee, not wearing a harness, was thrown clear from the bucket. As the bucket moved, the employee's legs hit the side of the bucket but the rest of his body missed, and he fell approximately 25 feet. He struck the bed of the truck, the new pole in the truck, and then hit the ground. The employee suffered major internal damage but remained conscious. The employee later died.

Keywords: Blunt force trauma, Bucket , Fall, Fall From Elevation, Fall Protection, Ground, Harness, Truck, Utility Pole

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 1751755.015 48 M Fatality Electricians
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.