Powered by GoogleTranslate

Inspection Detail

Inspection: 1697655 - R C Electric Inc

Inspection Information - Office: Tampa Area Office

 

Inspection Nr: 1697655
Report ID: 0420600
Date Opened: 06/29/1984

Site Address:
R C Electric Inc
75 Broad St
Masaryktown, FL 33512

Mailing Address:
24298 Mccaw Road, Brooksville, FL 33512

Union Status: NonUnion

SIC:1731

NAICS: 0 


Inspection Type: Accident

Scope: Complete

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 07/02/1984

Planning Guide: Safety-Construction

Emphasis:

Case Closed: 08/09/1984


Related Activity
Type Activity Nr Safety Health
Accident 360537906
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 2
Current Violations 2 2
Initial Penalty $400 $0 $0 $0 $0 $400
Current Penalty $400 $0 $0 $0 $0 $400
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19260301 A 07/19/1984 07/22/1984 $120 $120 $0 -  
2. 01002 Serious 19260400 C01 07/19/1984 07/22/1984 $280 $280 $0 -  

Investigation Summary

Investigation Nr: 14515720
Event: 06/28/1984
ELECTRIC SHOCK - CONTACT WITH LIVE PART THRU TOOL

AN ELECTRICIAN POSITIONED HIMSELF ON A STORAGE SHELF AND REMOVED A 2-FOOT-BY-4-FOOT CEILING TILE IN ORDER TO REACH A JUNCTION BOX. HE DID NOT HAVE ON A SHIRT, AND HIS STOMACH WAS IN CONTACT WITH THE GROUNDED CEILING TILE GRIDS. HE WAS GOING TO REMOVE ABOUT 0.5 INCHES OF INSULATION FROM AN ENERGIZED CONDUCTOR IN THE JUNCTION BOX. TO DO THIS, HE HAD ELECTRICIAN'S PLIERS WHICH HAD THE INSULATION REMOVED AT THE HANDLE TIPS. THE METAL HANDLE WAS IN CONTACT WITH HIS FOREARM, JUST BELOW THE WRIST, AS HE CUT INTO THE INSULATION ON THE CONDUCTOR. ELECTRIC CURRENT FLOWED THROUGH THE EMPLOYEE FROM HIS FOREARM TO HIS STOMACH, AND HE WAS ELECTROCUTED. THE COMPANY HAD NO ESTABLISHED LOCKOUT AND TAGGING PROCEDURE.

Keywords: ELECTRICAL, E C, ELECTRIC CONDUCTOR, ELECTRICIAN, ELECTROCUTED, LOCKOUT, ELECTRICAL BOX

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 1697655 Fatality Electric Shock Electricians
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close