Powered by GoogleTranslate

Inspection Detail

Inspection: 1635564 - Mastins Inc

Inspection Information - Office: Birmingham Area Office

 

Inspection Nr: 1635564
Report ID: 0418300
Date Opened: 08/21/1984

Site Address:
Mastins Inc
Main Street Middle School Gym
Centre, AL 35960

Mailing Address:
P O Box Q 105 So Main St, Boaz, AL 35957

Union Status: NonUnion

SIC:1731

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: Y

Ownership: Private

Safety/Health: Safety

Close Conference: 08/23/1984

Planning Guide: Safety-Construction

Emphasis:

Case Closed: 09/18/1984


Related Activity
Type Activity Nr Safety Health
Accident 360564355
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 2
Current Violations 2 2
Initial Penalty $770 $0 $0 $0 $0 $770
Current Penalty $770 $0 $0 $0 $0 $770
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001A Serious 19260400 A 09/05/1984 09/08/1984 $420 $420 $0 -  
2. 01001B Serious 19260400 C01 09/05/1984 09/08/1984 $0 $0 $0 -  
3. 01002A Serious 19260400 H01 09/05/1984 09/08/1984 $350 $350 $0 -  
4. 01002B Serious 19260402 C02 09/05/1984 09/08/1984 $0 $0 $0 -  

Investigation Summary

Investigation Nr: 14350367
Event: 08/16/1984
ELECTRIC SHOCK - DIRECT CONTACT WITH ENERGIZED PARTS

AN EMPLOYEE WAS CONNECTING A TWO-LAMP FIXTURE TO ENERGIZED TEMPORARY WIRING. HE WAS WORKING FROM A 6-FOOT WOODEN LADDER, AND HE WAS CLOSE TO THE METAL CEILING GRID. HE RECEIVED AN ELECTRIC SHOCK AND FELL TO THE FLOOR. WITHIN 20 MINUTES HE WAS TAKEN TO A HOSPITAL, WHERE A 1.5-HOUR RESUSCITATION EFFORT FAILED. HE WAS PRONOUNCED DEAD FROM ELECTRIC SHOCK AND CARDIAC ARREST. THE NEUTRAL CONDUCTOR OF THE TEMPORARY CIRCUIT HAD NOT BEEN IDENTIFIED, AND NO GFCI WAS PROVIDED.

Keywords: LIGHTING CIRCUIT, ELECTRICAL, ELECTROCUTED, ELECTRICAL WORK, LOCKOUT, TEMPORARY WIRING

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 1635564 Fatality Electric Shock Occupation not reported
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close