Powered by GoogleTranslate

Inspection Detail

Case Status: CLOSED

Inspection: 1628788.015 - 152974 - Wolfspeed, Inc.

Inspection Information - Office: Nc Department Of Labor - Raleigh

 

Inspection Nr: 1628788.015
Report ID: 0453710
Date Opened: 10/14/2022

Site Address:
152974 - Wolfspeed, Inc.
4600 Silicon Drive
Durham, NC 27703

Mailing Address:
4600 Silicon Drive, Durham, NC 27703

Union Status: NonUnion

SIC:3674

NAICS: 334413/Semiconductor and Related Device Manufacturing


Inspection Type: Fat/Cat

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 10/25/2022

Emphasis:

Case Closed: 06/12/2023


Related Activity
Type Activity Nr Safety Health
Accident 1958799
Case Status: CLOSED
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 2
Current Violations 2 2
Initial Penalty $27,553 $0 $0 $0 $0 $27,553
Current Penalty $27,553 $0 $0 $0 $0 $27,553
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19100138 A 04/14/2023 04/21/2023 $14,502 $14,502 $0 I - Informal Settlement  
2. 01002 Serious 19100335 A01 I 04/14/2023 04/21/2023 $13,051 $13,051 $0 I - Informal Settlement  

Investigation Summary

Investigation Nr: 150651.015
Event: 10/13/2022
Employee is killed when electrocuted

At 12:30 p.m. on October 13, 2022, a technician, working in the corrective maintenance section of the campus, observed a high resistance ground fault alarm at substation #6. The technician entered alone through a gated fence area to access the substation with his ARC flash gear and tools in hand. However, the technician did not put on his ARC flash gear to include gloves as he attempted to test the buss conductors. With his right hand, the technician reached into the bay and contacted the exposed coil to buss #3 and became the path to ground. The technician was found by an emergency response team member resting against the base of the bay with his right hand latched onto the coils and was unresponsive. After removal, using an insulted hook tool, the technician was determined to be dead.

Keywords: Electric Arc Flash, Electrocuted, Ground Fault, Unresponsive, Work Rules

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 1628788.015 45 M Fatality Occupation not reported
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close