Powered by GoogleTranslate

Inspection Detail

Inspection: 1617489 - R S Goodman Company Inc

Inspection Information - Office: Little Rock Area Office

 

Inspection Nr: 1617489
Report ID: 0627100
Date Opened: 06/22/1984

Site Address:
R S Goodman Company Inc
4400 Kinkead
Ft Smith, AR 72903

Mailing Address:
Po Box 698, Denison, TX 75020

Union Status: NonUnion

SIC:1623

NAICS: 0 


Inspection Type: Accident

Scope: Complete

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 06/26/1984

Planning Guide: Safety-Construction

Emphasis:

Case Closed: 04/17/1985


Related Activity
Type Activity Nr Safety Health
Accident 360576185
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $630 $0 $0 $0 $0 $630
Current Penalty $315 $0 $0 $0 $0 $315
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001A Serious 19260028 A 07/18/1984 07/21/1984 $315 $630 $0 08/09/1984 R - Review Commission  
2. 01001B Serious 19260950 B01 07/18/1984 07/21/1984 $0 $0 $0 08/09/1984 R - Review Commission  
3. 01001C Serious 19260950 D01 I 07/18/1984 07/21/1984 $0 $0 $0 08/09/1984 R - Review Commission  
4. 01001D Serious 19260954 F 07/18/1984 07/21/1984 $0 $0 $0 08/09/1984 R - Review Commission  

Investigation Summary

Investigation Nr: 14237630
Event: 06/21/1984
ELECTRIC SHOCK - DIRECT CONTACT WITH ENERGIZED PARTS

A power line worker was on a utility pole, connecting a transformer to a 120-volt secondary and a 7200-volt overhead power line. He apparently thought the 7200-volt primary was deenergized, so he was not wearing rubber insulating gloves. He connected the secondary conductors without trouble. However, another crew had energized a second section of overhead line connected to a second transformer that also supplied power to the 120-volt secondary. This energized the primary side of the transformer the power line worker was working on. When he touched the primary lead on the transformer, he was electrocuted.

Keywords: ELEC PROTECT EQUIP, OVERHEAD POWER LINE, ELECTRICAL, POWER LINE WORKER, ELECTROCUTED, LOCKOUT, E PTD, ELEC UTILITY WORK, TRANSFORMER, UTILITY POLE

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 1617489 Fatality Electric Shock Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.