Case Status: CLOSED

Inspection: 1572639.015 - Power Electronics Usa, Inc.

Inspection Information - Office: San Diego District Office

 

Inspection Nr: 1572639.015
Report ID: 0950632
Date Opened: 01/13/2022

Site Address:
Power Electronics Usa, Inc.
7096 English Road
Calipatria, CA 92233

Mailing Address:
1510 N Hobson St., Gilbert, AZ 85233

Union Status: NonUnion

SIC:

NAICS: 221114 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 06/20/2022

Emphasis:

Case Closed: 07/31/2023


Related Activity
Type Activity Nr Safety Health
Accident 1853532
Case Status: CLOSED
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 4 4 8
Current Violations 4 4 8
Initial Penalty $72,000 $0 $0 $2,895 $0 $74,895
Current Penalty $58,500 $0 $0 $1,980 $0 $60,480
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other 3203(B)(2) 06/20/2022 08/05/2022 $300 $375 $0 06/21/2022 O - Administrative Law Judge Order  
2. 01002 Other 2940(G)(1)(B) 06/20/2022 08/05/2022 $560 $840 $0 06/21/2022 O - Administrative Law Judge Order  
3. 01003 Other 3203(A) 06/20/2022 08/05/2022 $560 $840 $0 06/21/2022 O - Administrative Law Judge Order  
4. 01004 Other 3395(I) 06/20/2022 $560 $840 $0 06/21/2022 O - Administrative Law Judge Order  
5. 02001 Serious 2940(C) 06/20/2022 07/05/2022 $6,750 $18,000 $0 06/21/2022 O - Administrative Law Judge Order  
6. 03001 Serious 29400011 B 06/20/2022 $22,500 $22,500 $0 06/21/2022 O - Administrative Law Judge Order  
7. 04001 Serious 29400013 G02 06/20/2022 $22,500 $22,500 $0 06/21/2022 O - Administrative Law Judge Order  
8. 05001 Serious 2944(G) 06/20/2022 $6,750 $9,000 $0 06/21/2022 O - Administrative Law Judge Order  

Investigation Summary

Investigation Nr: 146321.015
Event: 01/04/2022
Employee sustains severe upper body burns from arc flash

At 1:30 p.m. on January 4, 2022, Employee #1, an electrician, was working at a solar farm. Employee #1 and his coworker were tasked with troubleshooting and servicing four inverters manufactured by Power Electronics that had module failures. They completed troubleshooting and servicing the first inverter and began working on the second inverter. Employee #1 identified a fault in an AC fuse. The coworker went to get his tools while Employee #1 positioned himself in front of the inverter door. They had switched pre-established work assignments and were not following the pre-established methodology They did not disconnect the power from the main AC switch. Employee #1 opened the inverter's door where the faulty module was identified. He started to remove the protective methacrylate shield to replace the fuse while he was talking to his coworker about personal matters when an arc flash occurred. Employee #1, who was kneeling in front of the module, sustained serious electrical burn injuries to his face, arms, and chest. He was hospitalized.

Keywords: Burn, Electric Arc, Electric Arc Flash, Electrical, Electrical Burn, Electrician, Fuse, Lockout/Tagout, Maintenance, Repair, Troubleshooting

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 1572639.015 28 M Hospitalized injury Electricians
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.