Powered by GoogleTranslate

Inspection Detail

Case Status: CLOSED

Inspection: 1549748.015 - Olon Ricerca Bioscience, Llc

Inspection Information - Office: Cleveland Area Office

 

Inspection Nr: 1549748.015
Report ID: 0522300
Date Opened: 08/25/2021

Site Address:
Olon Ricerca Bioscience, Llc
7528 Auburn Road
Painesville, OH 44077

Mailing Address:
7528 Auburn Road, Painesville, OH 44077

Union Status: NonUnion

SIC:

NAICS: 541715 


Inspection Type: Referral

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 08/25/2021

Emphasis: P:Piv, L:Piv

Case Closed: 03/07/2022


Related Activity
Type Activity Nr Safety Health
Referral 1801512 Yes
Case Status: CLOSED
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 7 7
Current Violations 7 7
Initial Penalty $61,446 $0 $0 $0 $0 $61,446
Current Penalty $39,935 $0 $0 $0 $0 $39,935
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19100147 C06 I C 11/15/2021 01/03/2022 $5,705 $8,778 $0 I - Informal Settlement  
2. 01002 Serious 19100303 E01 II 11/15/2021 $5,705 $8,778 $0 I - Informal Settlement  
3. 01003A Serious 19100303 H05 III A 11/15/2021 $5,705 $8,778 $0 I - Informal Settlement  
4. 01003B Serious 19100303 H05 III B 11/15/2021 $0 $0 $0 I - Informal Settlement  
5. 01004 Serious 19100332 B03 11/15/2021 01/03/2022 $5,705 $8,778 $0 I - Informal Settlement  
6. 01005 Serious 19100333 A02 11/15/2021 01/03/2022 $5,705 $8,778 $0 I - Informal Settlement  
7. 01006 Serious 19100334 C03 11/15/2021 $5,705 $8,778 $0 I - Informal Settlement  
8. 01007 Serious 19100335 A01 I 11/15/2021 $5,705 $8,778 $0 I - Informal Settlement  

Investigation Summary

Investigation Nr: 138530.015
Event: 08/22/2021
Employee sustains burns in arc blast contacting conductor

At 1:30 p.m. on August 22, 2021, an employee working as an operations and maintenance technician for a bioscience research facility was troubleshooting an electrical system. The employee was investigating a power outage in Building B. The employee and a coworker, the facility supervisor, began troubleshooting the outage. The employee reset a switch in the outdoor substation, but the power did not return. The employee attempted to take a reading on one of the four lines that comes from the substation to an indoor 4160-Volt 6-Amp feeder. The feeder is located at Unit Substation 4 located in the penthouse of Building B. The employee opened a medium voltage transformer to access a switch located in the metal enclosed electrical cabinet to take a reading on the fuses when he caused an arc flash/blast. The employee was not wearing proper personal protective equipment, using proper electrical tools and had not received proper training in the high voltage electrical work. The employee was hospitalized to treat electrical shock and burns to his chest, arms, hands and fingers.

Keywords: Arm, Burn, Chest, Conductor, Electric Arc, Electric Arc Flash, Electric Shock, Electrical, Electrical Box, Electrical Burn, Electrical Cabinet, Electrical Wire, Electrical Work, Engineering Controls, Finger, Hand, Lack of Engineering Controls, Lack of Work Procedures, Lockout, Lockout/Tagout, Maintenance, PPE, PPE Hazard Assessment, Protective Clothing, Shock, Technician, Training, Transformer, Troubleshooting, Wrong Equipment

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 1549748.015 53 M Hospitalized injury
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.