Inspection: 1537166.015 - Calpine Operating Services Company, Inc.

Inspection Information - Office: Corpus Christi Area Office

 

Inspection Nr: 1537166.015
Report ID: 0626000
Date Opened: 06/18/2021

Site Address:
Calpine Operating Services Company, Inc.
3952 Buddy Lawrence Drive
Corpus Christi, TX 78407

Mailing Address:
3952 Buddy Lawrence Drive, Corpus Christi, TX 78407

Union Status: NonUnion

SIC:

NAICS: 221118 


Inspection Type: Fat/Cat

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 11/01/2021

Emphasis:

Case Closed: 06/10/2022


Related Activity
Type Activity Nr Safety Health
Accident 1778508
Case Status: CLOSED
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $13,653 $0 $0 $0 $0 $13,653
Current Penalty $13,653 $0 $0 $0 $0 $13,653
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 5A0001 10/29/2021 05/31/2022 $13,653 $13,653 $0 I - Informal Settlement  

Investigation Summary

Investigation Nr: 136398.015
Event: 06/18/2021
Power plant worker is killed when struck by vessel lid

At 6:30 p.m. on June 18, 2021, an employee was working for a firm that operated electric power generation facilities. He was working at a natural gas-fired power plant. He and a coworker were restoring a natural gas filter system at the power plant, by aligning valves after a maintenance crew had replaced filter media. This system separated liquids from the natural gas before the natural gas was burned as fuel gas to heat water and produce steam for turbines. This was Filtering Unit A. It had been taken offline for the filter media replacement. It was a model number 95V-W12A-I-18-550-WP vertical dry gas scrubber, with tag number ONG01FA. Once the filter change had been completed, there were two draw bolts that should have been tightened to 354 lb-ft (480 newton-meters) of torque. The workers were not aware of the manufacturer's torque requirements. They used crescent wrenches to tighten the bolts. They did not use a torque wrench or a pneumatic tool. There were additional spacing tolerance requirements of which the workers were unaware. When they placed the natural gas coalescing filter vessel back into service, the vessel lid blew off. It struck the employee and knocked him off a scaffold. He suffered blunt force trauma, and he was killed.

Keywords: Blunt force, Blunt force trauma, E PTD (power generation), Electrical, Fall, Flying Object, Inadequate Maint, Natural Gas, Pressure Vessel, Scaffold, Struck By, Training, Traumatic

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 1537166.015 37 M Fatality
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.