Powered by GoogleTranslate

Inspection Detail

Inspection: 15319577 - Lord Electric Co Of P R Inc

Inspection Information - Office: Pr-E-Arecibo 0257210

 

Inspection Nr: 15319577
Report ID: 0257210
Date Opened: 02/26/1985

Site Address:
Lord Electric Co Of P R Inc
Carr 689 K.1.9
Vega Baja, PR 00763

Mailing Address:
Aptdo 3408, San Juan, PR 00936

Union Status: Union

SIC:1731

NAICS: 0 


Inspection Type: Unprog Rel

Scope: Complete

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 04/09/1985

Planning Guide: Safety-Construction

Emphasis:

Case Closed: 07/15/1985


Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 2
Current Violations 2 2
Initial Penalty $0 $0 $0 $0 $0 $0
Current Penalty $0 $0 $0 $0 $0 $0
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other 19260451 A13 05/14/1985 05/21/1985 $0 $0 $0 -  
2. 01002 Other 19260451 D03 05/14/1985 05/17/1985 $0 $0 $0 -  

Investigation Summary

Investigation Nr: 14461404
Event: 02/25/1985
ELECTRIC SHOCK - DIRECT CONTACT WITH ENERGIZED PARTS

Four employees were assigned to dismantle metal shelves and store them in a building that was to be used as a warehouse. The employees were working in the open, in front of the warehouse, when it began raining heavily. Because the door to the warehouse was locked, the employees ran for shelter in a metal cabinet housing transformers. The transformer cabinet was marked "Restricted Area" and "High Voltage." The back door of the cabinet was open, exposing bare, energized conductors. Apparently, one of the employees stepped into the cabinet and contacted the 13-kilovolt conductors. He was electrocuted. A second employee also contacted energized parts and received an electric shock. He was hospitalized for his injuries.

Keywords: ELECTRICAL, ELECTRIC SHOCK, UNTRAINED, E GI V, ELECTROCUTED, UNGUARDED LIVE PARTS, TRANSFORMER

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 15319577 Occupation Not Listed
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.