Inspection: 15305097 - Barnes & Powell Electrical Company Inc
Inspection Information - Office: Nc Department Of Labor - Raleigh
Site Address:
Barnes & Powell Electrical Company Inc
304 South Parker Street
Elm City, NC 27822
Mailing Address:
Po Box 849, Elm City, NC 27822
Union Status: NonUnion
SIC:1731
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 08/27/1986
Emphasis:
Case Closed: 10/28/1986
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 360768519 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 1 | 1 | 2 | |||
| Current Violations | 1 | 1 | 2 | |||
| Initial Penalty | $400 | $0 | $0 | $0 | $0 | $400 |
| Current Penalty | $400 | $0 | $0 | $0 | $0 | $400 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Serious | 19260400 G01 | 09/30/1986 | 10/03/1986 | $400 | $400 | $0 | - | ||
| 2. | 02001 | Other | 7B0302 A | 09/30/1986 | 10/03/1986 | $0 | $0 | $0 | - |
Investigation Summary
AN ELECTRICIAN WAS SPLICING A BONDING CABLE BETWEEN TWO AIRPORT RUNWAY LIGHTS. THE DISCONNECTING MEANS FOR THE LIGHTS WAS ABOUT 900 FEET FROM HIS WORK AREA, SO A HELPER WAS OPENING AND CLOSING THE DISCONNECTING MEANS IN RESPONSE TO PREARRANGED SIGNALS. IT WAS DARK, SO THE EMPLOYEES WERE USING A FLASHLIGHT FOR SIGNALLING PURPOSES. THE WEATHER WAS CLEAR, BUT THE NIGHT WAS DARK, AND THE TWO EMPLOYEES COULD NOT REMAIN IN CONTINUAL VISUAL CONTACT. DURING THIS PROCESS, THE HELPER THOUGHT HE SAW THE FLASHLIGHT SIGNAL AND ENERGIZED THE CIRCUIT. UNFORTUNATELY, THE ELECTRICIAN WAS IN CONTACT WITH THE CIRCUIT CONDUCTORS AT THE TIME, AND THE CIRCUIT WAS ENERGIZED AT 5000 VOLTS. THE ELECTRICIAN WAS ELECTROCUTED.
Keywords: E GI IV, ELECTRICAL, ELECTROCUTED, ELECTRICAL WORK, LOCKOUT, ELECTRIC CONDUCTOR
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 15305097 | Fatality | Electric Shock | Electricians |