Inspection Detail
Inspection: 15261746 - Husky Rmt Properties Inc
Inspection Information - Office: Wyoming Department Of Workforce Services - Osha Division
Site Address:
Husky Rmt Properties Inc
2700 East 5th St
Cheyenne, WY 82007
Mailing Address:
Po Box 1588, Cheyenne, WY 82005
Union Status: Union
SIC:2911
NAICS: 0
Inspection Type: Accident
Scope: Complete
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 01/09/1985
Emphasis: L:Manuf
Case Closed: 03/04/1985
Type | Activity Nr | Safety | Health |
---|---|---|---|
Accident | 360607584 |
Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
---|---|---|---|---|---|---|
Initial Violations | 1 | 2 | 3 | |||
Current Violations | 1 | 2 | 3 | |||
Initial Penalty | $540 | $0 | $0 | $0 | $0 | $540 |
Current Penalty | $540 | $0 | $0 | $0 | $0 | $540 |
FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
# | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
---|---|---|---|---|---|---|---|---|---|---|---|
1. | 01001 | Serious | GN090003 E3A | 02/19/1985 | 02/21/1985 | $540 | $540 | $0 | - | ||
2. | 02001 | Other | GN090003 B5 | 02/19/1985 | 03/02/1985 | $0 | $0 | $0 | - | ||
3. | 02002 | Other | GN090003 F2B | 02/19/1985 | 03/02/1985 | $0 | $0 | $0 | - |
Investigation Summary
THE PRESSURE RELIEF VALVE BETWEEN THE ISO STRIPPER AND THE BLOWDOWN LINE FAILED ON SUNDAY, DECEMBER 16. THE FAILED VALVE WAS REMOVED ON THE FOLLOWING TUESDAY. THE BLOWDOWN LINE ON THE ISO STRIPPER SIDE WAS TO BE CLOSED OFF WITH A BLOCK VALVE UNTIL THE RELIEF VALVE COULD BE REPLACED. THERE WAS A POWER OUTAGE AT THE PLATFORMER UNIT WHICH CAUSED THE SULFER UNIT TO SHUT DOWN. A BLOCK VALVE AT THE PLATFORMER WAS OPENED, CAUSING HYDROGEN SULFIDE TO VENT INTO THE BLOWDOWN LINE. HYDROGEN SULFIDE VENTED FROM THE OPEN END OF THE BLOWDOWN LINE AT THE ISO STRIPPER BECAUSE THE BLOCK VALVE HAD NOT BEEN CORRECTLY INSTALLED (NO BLIND WAS INSTALLED). THE LAST TIME THE TWO EMPLOYEES WERE SEEN BEFORE THE ACCIDENT THEY WERE WEARING THEIR AIR MASKS. WHEN THE EMPLOYEES WERE FOUND AFTER THE ACCIDENT, EMPLOYEE #2 HAD HIS MASK PARTIALLY ON AND WAS LOCATED APPROXIMATELY 8 FEET NORTH OF THE WORK AREA. EMPLOYEE #1 WAS ON THE RECEIVER, APPROXIMATELY 15 FEET NORTHWEST OF THE WORK AREA, AND WAS NOT WEARING AN AIR MASK. THE TEMPERATURE ON DAY OF THE ACCIDENT WAS 13 DEGREES F. THERE WAS NO SPOTTER ASSIGNED TO ASSIST THE EMPLOYEES IN THE EVENT OF AN EMERGENCY.
Keywords: RESPIRATORY, HYDROGEN SULFIDE, WORK RULES, INHALATION, TOXIC FUMES, INATTENTION, RESPIRATOR
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 15261746 | Hospitalized injury | Asphyxia | Plumbers, pipefitters and steamfitters | ||
2 | 15261746 | Fatality | Asphyxia | Plumbers, pipefitters and steamfitters |