Powered by GoogleTranslate

Inspection Detail

Inspection: 15210743 - Utility Construction Corp

Inspection Information - Office: Vt Department Of Labor - Vosha

 

Inspection Nr: 15210743
Report ID: 0155010
Date Opened: 08/03/1984

Site Address:
Utility Construction Corp
North Ave
Burlington, VT 05401

Mailing Address:
Valley View, Woodstock, VT 05091

Union Status: Union

SIC:1623

NAICS: 0 


Inspection Type: Referral

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 08/08/1984

Planning Guide: Safety-Construction

Emphasis:

Case Closed: 06/03/1985


Related Activity
Type Activity Nr Safety Health
Referral 900598186 Yes
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $140 $0 $0 $0 $0 $140
Current Penalty $0 $0 $0 $0 $0 $0
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001A Serious 19260950 E01 08/31/1984 09/03/1984 $140 $140 $0 09/26/1984 L - State Settlement Citation has been deleted.
2. 01001B Other 19260020 B01 08/11/1984 08/14/1984 $0 $0 $0 09/26/1984 L - State Settlement  

Investigation Summary

Investigation Nr: 14467674
Event: 08/03/1984
ELECTRIC SHOCK - CONTACT WITH EXPOSED ENERGIZED PARTS

AN EMPLOYEE USING RUBBER GLOVES WAS WORKING ON A 13.8-KILOVOLT (PHASE TO PHASE) CIRCUIT FROM A FIBERGLASS INSULATED BUCKET OF A HYDRAULIC AERIAL LIFT (1974 TELBOW: MODEL T45 169 AE) MOUNTED ON A 1974 INTERNATIONAL TRUCK. THE EMPLOYEE'S UPPER ARM MADE ACCIDENTAL CONTACT WITH THE TOP SIDE OF A LIGHTNING ARRESTER (ENTRY POINT AT 7980 VOLTS PHASE TO GROUND) WHILE HIS RIGHT ABDOMENAL AREA WAS IN CONTACT WITH A BARE CONDUCTOR RUNNING TO THE GROUNDED NEUTRAL (EXIT POINT). THE EMPLOYEE WAS WEARING GLOVES, BUT NOT SLEEVES. HE WAS ELECTROCUTED.

Keywords: LIGHTNING ARRESTER, ELECTRICAL, POWER LINE WORKER, E PTD, ELEC UTILITY WORK, ELECTRIC SHOCK, AERIAL LIFT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 15210743 Hospitalized injury Electric Shock Supervisors; electricians & power transm. install.
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close