Powered by GoogleTranslate

Inspection Detail

Inspection: 15193626 - Dixie Escalante Rural Elect Ass Inc

Inspection Information - Office: Utah Division Of Occupational Safety And Health

 

Inspection Nr: 15193626
Report ID: 0854910
Date Opened: 04/19/1984

Site Address:
Dixie Escalante Rural Elect Ass Inc
2 Mi West Of Beryl Cross Roads
Beryl, UT 89714

Mailing Address:
, , 00000

Union Status: NonUnion

SIC:4911

NAICS: 0 


Inspection Type: Accident

Scope: Complete

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 07/10/1984

Emphasis:

Case Closed: 07/01/2016


Related Activity
Type Activity Nr Safety Health
Accident 360600555
Inspection 14455422
Inspection 14456172
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 3 3
Current Violations 3 3
Initial Penalty $0 $0 $0 $0 $0 $0
Current Penalty $0 $0 $0 $0 $0 $0
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other GEN01060234 05/22/1984 06/12/1984 $0 $0 $0 -  
2. 01002 Other GEN01060734 4 05/22/1984 06/28/1984 $0 $0 $0 -  
3. 01003 Other GEN02430303 05/22/1984 06/28/1984 $0 $0 $0 -  

Investigation Summary

Investigation Nr: 14456172
Event: 04/18/1984
ELECTRIC SHOCK - GROUND FAULT IN OVERHEAD LINE SWITCH

AN EMPLOYEE WAS ASSISTING A CREW IN A LOAD SWITCHING OPERATION. HE WAS STANDING ON THE GROUND, LEANING AGAINST A METAL FENCE, OPERATING A GOAB SWITCH. THE SWITCH WAS DESIGNED TO PERMIT SWITCHING LOADS FROM THE GROUND. THE SWITCHING MECHANISM INCORPORATED A FLEXIBLE METAL BAND, WHICH WAS TO REMAIN IN CONTACT WITH THE ENERGIZED SIDE OF THE SWITCH UNTIL THE PRIMARY MECHANISM REESTABLISHED CONTACT. THE METAL BAND WAS INTENDED TO PREVENT ARCING AT THE SWITCH. HOWEVER, THE BAND WAS MISALIGNED; AND, WHEN THE PRIMARY MECHANISM SEPARATED, AN ELECTRIC ARC FORMED BETWEEN THE ENERGIZED PARTS OF THE SWITCH AND SOME OF THE NON-CURRENT-CARRYING HARDWARE ON THE POLE. THE EMPLOYEE RECEIVED AN ELECTRIC SHOCK WHEN HE OPENED THE GOAB SWITCH. THE CURRENT ENTRY AND EXIT POINTS WERE THE EMPLOYEE'S HANDS, HIS RIGHT SIDE AT THE WAISTLINE, AND HIS RIGHT LEG. THE EMPLOYEE WAS HOSPITALIZED FOR HIS INJURIES.

Keywords: ELECTRIC ARC, OVERHEAD POWER LINE, ELECTRICAL, CUTOUT SWITCH, GROUND FAULT, ELECTRIC SHOCK, BURN, POWER LINE WORKER, E PTD, ELEC UTILITY WORK

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 15193626 Hospitalized injury Electric Shock Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close