Inspection Detail
Inspection: 15133390 - Lake Cunningham Fire Dept
Inspection Information - Office: Sc Department Of Labor, Licensing, And Regulation
Site Address:
Lake Cunningham Fire Dept
Hwy 101 North
Greer, SC 29651
Mailing Address:
Rt 9 Box 538, Greer, SC 29651
Union Status: NonUnion
SIC:9224
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 07/19/1984
Planning Guide: Safety-Manufacturing
Emphasis:
Case Closed: 08/20/1984
Type | Activity Nr | Safety | Health |
---|---|---|---|
Accident | 360598155 |
Investigation Summary
WHILE FIGHTING A TRAILER FIRE, TWO FIREMEN WERE RECEIVING ELECTRIC SHOCKS EVEN THOUGH THE ELECTRIC METER HAD BEEN PULLED AND THOUGH THE FIREMEN WERE WEARING FULL TURNOUT GEAR. THE ELECTRIC UTILITY WAS CALLED, AND THE ELECTRIC SERVICE WAS DISCONNECTED AT THE TRANSFORMER POLE. THE NEUTRAL AND PHASE CONDUCTORS HAD BEEN FUSED TOGETHER, WHICH CAUSED THE RELATIVE VOLTAGE ON THE NEUTRAL TO RISE. THIS IN TURN HAD ENERGIZED THE METER BASE.
Keywords: FIREFIGHTER, SERVICE CONDUCTOR, ELECTRICAL, E GI VII, FIRE, ELECTRIC METER, GROUND FAULT, ELECTRIC SHOCK
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 15133390 | Hospitalized injury | Electric Shock | Firefighting occupations | ||
2 | 15133390 | Hospitalized injury | Electric Shock | Firefighting occupations |