Powered by GoogleTranslate

Inspection Detail

Case Status: CLOSED

Inspection: 1511027.015 - Alliant Energy

Inspection Information - Office: Appleton Area Office

 

Inspection Nr: 1511027.015
Report ID: 0521100
Date Opened: 01/21/2021

Site Address:
Alliant Energy
4811 Venture Drive
Sheboygan, WI 53083

Mailing Address:
4421 Tower Drive, Sheboygan, WI 53081

Union Status: Union

SIC:

NAICS: 237130/Power and Communication Line and Related Structures Construction


Inspection Type: Fat/Cat

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 01/21/2021

Emphasis:

Case Closed: 12/07/2021


Related Activity
Type Activity Nr Safety Health
Accident 1723612
Referral 1723026 Yes
Referral 1724640 Yes
Referral 1723005 Yes
Case Status: CLOSED
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $13,653 $0 $0 $0 $0 $13,653
Current Penalty $13,653 $0 $0 $0 $0 $13,653
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19100269 C01 I 05/19/2021 06/17/2021 $13,653 $13,653 $0 I - Informal Settlement  

Investigation Summary

Investigation Nr: 132756.015
Event: 01/21/2021
One employee is electrocuted and another is burned by offsit

At 11:00 a.m. on January 21, 2021, Employees #1 and #2 and two coworkers, employed by an energy supply company, were responding to a call from a contractor who was excavating a 200-foot water line addition to a meat market, a multiemployer construction project. The contractor had struck an underground power line between transformer 1 and transformer 2 while excavating. The power line break caused power to be lost at the meat market and a neighboring facility. The four energy supply company employees were working to repair the broken underground power lines. Employee #2 shut the power off at the pole and placed grounding straps on the secondary compartment of transformer 1. Employee #2 joined Employee #1 on the west side of the excavation while their coworkers worked elsewhere. When the power was interrupted, a generator in the facility next door started automatically and began providing power to the facility's office. Approximately 30 minutes later, an employee from the neighboring facility threw a manual switch connected to a generator to supply electricity to the facility's warehouse. The electricity back-fed through the ungrounded transformer 2 to where Employees #1 and Employee #2 were working. Both employees received an electric shock from the backfeed. Employee #1 was killed by electrocution. Employee #2 sustained severe burns to the hands. Employee #2 was transported by emergency services to the hospital, where he was admitted for treatment of the electrical burns.

Keywords: Burn, Construction, Electric Shock, Electrocuted, Equipment Grounding, Excavation, Lockout/Tagout, Multiemployer, Repair, Transformer, Undrgrd Power Line, Voltage Backfeed

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 1511027.015 26 M Hospitalized injury Electrical power installers and repairers
2 1511027.015 58 M Fatality Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close