Powered by GoogleTranslate

Inspection Detail

Case Status: CLOSED

Inspection: 1507500.015 - Shermco Industries Inc

Inspection Information - Office: Dallas Area Office

 

Inspection Nr: 1507500.015
Report ID: 0626300
Date Opened: 12/21/2020

Site Address:
Shermco Industries Inc
2601 N Floyd Road (Utd Energy Plant Doghouse #2)
Richardson, TX 75080

Mailing Address:
2425 E Pioneer Dr, Irving, TX 75061

Union Status: NonUnion

SIC:

NAICS: 221121/Electric Bulk Power Transmission and Control


Inspection Type: Referral

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 12/21/2020

Emphasis:

Case Closed: 11/22/2022


Related Activity
Type Activity Nr Safety Health
Referral 1708955 Yes
Inspection 1511533 Yes
Case Status: CLOSED
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 4 4
Current Violations 2 2
Initial Penalty $54,612 $0 $0 $0 $0 $54,612
Current Penalty $0 $0 $0 $27,306 $0 $27,306
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other 19100269 A03 III 05/28/2021 06/14/2022 $13,653 $13,653 $0 06/25/2021 F - Formal Settlement  
2. 01002A Serious 19100269 C01 I 05/28/2021 06/24/2021 $0 $13,653 $0 06/25/2021 F - Formal Settlement Citation has been deleted.
3. 01002B Serious 19100269 C05 05/28/2021 06/24/2021 $0 $0 $0 06/25/2021 F - Formal Settlement Citation has been deleted.
4. 01003A Other 19100269 L01 III 05/28/2021 06/14/2022 $13,653 $13,653 $0 06/25/2021 F - Formal Settlement  
5. 01003B Serious 19100269 M02 I 05/28/2021 06/24/2021 $0 $0 $0 06/25/2021 F - Formal Settlement Citation has been deleted.
6. 01003C Serious 19100269 M03 II 05/28/2021 06/24/2021 $0 $0 $0 06/25/2021 F - Formal Settlement Citation has been deleted.
7. 01004 Serious 19100269 L08 V 05/28/2021 06/24/2021 $0 $13,653 $0 06/25/2021 F - Formal Settlement Citation has been deleted.

Investigation Summary

Investigation Nr: 131886.015
Event: 12/19/2020
Employee experiences electrical contact/arc event leading to

At 9:18 a.m. on December 19, 2020, an employee was conducting visual inspections of electrical equipment, specifically inspecting the backside of the breakers within the doghouse panels. While working alone, the employee was found with his upper body inside the back panel of the main breaker for the doghouse, with his head positioned between two phases of the breaker, each carrying 1,480 volts. An electrical contact/arc event occurred at the employee's head and both hands. The primary feed could not be shut off, and the secondary feed within the doghouse had been tripped, allowing 1,480 volts across three phases to enter the back of the main breaker while the rest of the doghouse and the plant remained deenergized. The incident resulted in electrical burns to both hands and a large cauterized laceration on the right hand, leading to the amputation of both hands. The employee was hospitalized.

Keywords: Amputation, Electric Arc Flash, Hand, Head, Inspection, Laceration

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 1507500.015 24 M Hospitalized injury Electrical and electronic technicians
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.