Powered by GoogleTranslate

Inspection Detail

Inspection: 1500602 - Rocky Mountain Natural Gas Company,Inc.

Inspection Information - Office: Denver Area Office

 

Inspection Nr: 1500602
Report ID: 0830500
Date Opened: 12/17/1985

Site Address:
Rocky Mountain Natural Gas Company,Inc.
0934 164 Rd.
Glenwood Springs, CO 81601

Mailing Address:
420 Capitol Life 1600 Sherman St., Denver, CO 80203

Union Status: NonUnion

SIC:4924

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 02/28/1986

Emphasis:

Case Closed: 03/27/1986


Related Activity
Type Activity Nr Safety Health
Accident 360554844
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 2
Current Violations 2 2
Initial Penalty $2,000 $0 $0 $0 $0 $2,000
Current Penalty $1,200 $0 $0 $0 $0 $1,200
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19100110 B06 I 03/14/1986 03/16/1986 $600 $1,000 $0 I - Informal Settlement  
2. 01002 Serious 19100110 B16 03/14/1986 03/16/1986 $600 $1,000 $0 I - Informal Settlement  

Investigation Summary

Investigation Nr: 14426969
Event: 12/16/1985
PROPANE GAS RELEASED INTO BUILDING; EXPLOSION OCCURRED

EMPLOYEES #1 THROUGH #27 WERE WORKING AT THEIR REGULARLY ASSIGNED TASKS IN A TWO STORY OPERATIONS OFFICE. EMPLOYEE #20 DROVE A 1982, MODEL 437, INTERNATIONAL TRUCK, PULLING A 1982 AZTEC FLATBED, INTO THE GARAGE AREA OF THE BUILDING. THE FLATBED HAD A 1,000 GALLON PROPANE TANK CHAINED ONTO IT. EMPLOYEE #1 WAS ATTACHING DECALS TO THE SIDE OF THE TANK TO MEET DEPARTMENT OF TRANSPORTATION REGULATIONS. EMPLOYEE #20 WAS REMOVING FOUR BOLTS AT THE END OF THE TANK TO CHECK ON A A POSSIBLY DEFECTIVE LIQUID LEVEL GAUGE. EMPLOYEE #20 DIDN'T REALIZE THE GAUGE WAS A FLOAT GAUGE, AND THAT REMOVING IT WOULD RELEASE THE PROPANE. THE GAUGE WAS REMOVED, RELEASING PROPANE FROM THE TANK INTO THE LOWER LEVEL OF THE BUILDING. A SPACE HEATER IGNITED THE PROPANE, CAUSING AN EXPLOSION. THE ENTIRE BUILDING WAS DESTROYED. THE SECOND STORY OF THE BUILDING COLLAPSED ONTO THE GROUND FLOOR. FIRE CONSUMED A GREAT DEAL OF THE BUILDING'S CONTENTS. EMPLOYEES #1 THROUGH #12 DIED IN THE EXPLOSION OR FIRE, WHILE EMPLOYEES #13 THROUGH 27 WERE HOSPITALIZED FOR A WIDE VARIETY OF INJURIES.

Keywords: MAINTENANCE, COLLAPSE, FLAMMABLE VAPORS, FIRE, EXPLOSION, GAS LEAK, PROPANE

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 1500602 Fatality Burn/Scald(Heat) Occupation not reported
2 1500602 Hospitalized injury Dislocation Occupation not reported
3 1500602 Hospitalized injury Asphyxia Occupation not reported
4 1500602 Hospitalized injury Fracture Occupation not reported
5 1500602 Hospitalized injury Burn/Scald(Heat) Occupation not reported
6 1500602 Hospitalized injury Fracture Occupation not reported
7 1500602 Hospitalized injury Burn/Scald(Heat) Occupation not reported
8 1500602 Hospitalized injury Fracture Occupation not reported
9 1500602 Hospitalized injury Concussion Occupation not reported
10 1500602 Hospitalized injury Dislocation Occupation not reported
11 1500602 Hospitalized injury Bruise/Contus/Abras Occupation not reported
12 1500602 Hospitalized injury Bruise/Contus/Abras Occupation not reported
13 1500602 Hospitalized injury Bruise/Contus/Abras Occupation not reported
14 1500602 Hospitalized injury Cut/Laceration Occupation not reported
15 1500602 Hospitalized injury Fracture Occupation not reported
16 1500602 Fatality Burn/Scald(Heat) Occupation not reported
17 1500602 Fatality Burn/Scald(Heat) Occupation not reported
18 1500602 Fatality Burn/Scald(Heat) Occupation not reported
19 1500602 Fatality Burn/Scald(Heat) Occupation not reported
20 1500602 Fatality Burn/Scald(Heat) Occupation not reported
21 1500602 Fatality Burn/Scald(Heat) Occupation not reported
22 1500602 Fatality Burn/Scald(Heat) Occupation not reported
23 1500602 Fatality Burn/Scald(Heat) Occupation not reported
24 1500602 Fatality Burn/Scald(Heat) Occupation not reported
25 1500602 Fatality Burn/Scald(Heat) Occupation not reported
26 1500602 Fatality Burn/Scald(Heat) Occupation not reported
27 1500602 Hospitalized injury Fracture Occupation not reported
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.