Powered by GoogleTranslate

Inspection Detail

Inspection: 14975312 - South River Electric Membership Co-Op Inc

Inspection Information - Office: Nc Department Of Labor - Raleigh

 

Inspection Nr: 14975312
Report ID: 0453710
Date Opened: 04/03/1984

Site Address:
South River Electric Membership Co-Op Inc
Sr-2041 & 2042
Steadman, NC 28391

Mailing Address:
701 E Broad St, Dunn, ST 28334

Union Status: NonUnion

SIC:4911

NAICS: 0 


Inspection Type: Accident

Scope: Complete

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 04/03/1984

Planning Guide: Safety-Construction

Emphasis:

Case Closed: 05/21/1984


Related Activity
Type Activity Nr Safety Health
Accident 360593552
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $480 $0 $0 $0 $0 $480
Current Penalty $480 $0 $0 $0 $0 $480
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19260950 D01 IIA 05/11/1984 05/25/1984 $480 $480 $0 -  

Investigation Summary

Investigation Nr: 14446256
Event: 03/31/1984
ELECTRIC SHOCK - DIRECT CONTACT WITH OVERHEAD POWER LINE

A LINEMAN CLIMBED A UTILITY POLE TO PROVIDE A TEMPORARY REPAIR OF LINE DAMAGE THAT HAD BEEN CAUSING A POWER OUTAGE. IN ORDER TO DO THIS, A JUMPER WIRE ON THE LEFT SIDE OF THE POLE WAS TO BE CONNECTED TO THE TOP WIRE ON THE RIGHT SIDE OF THE POLE. THIS WOULD PROVIDE A SINGLE-PHASE 7200-VOLT CIRCUIT FEEDING IN BOTH DIRECTIONS AND WOULD TEMPORARILY SUPPLY ELECTRIC POWER TO HOMES IN THE AREA. A SERVICE MAN HAD GONE 2 MILES AWAY TO PULL THE DISCONNECT SWITCH SO THAT THE LINEMAN COULD CONNECT THE JUMPER WIRE TO THE PHASE WITH AN 8-FOOT HOT STICK WHILE THE LINE WAS DEENERGIZED. WITH THE DISCONNECT SWITCH OPEN, ALL THREE LINES ON THE RIGHT SIDE WOULD HAVE BEEN DEENERGIZED. THE LINE FOREMAN WENT TO THE TRUCK TO GET A RADIO. AT THIS TIME, THE LINEMAN HAD MOVED HIS SAFETY BELT TIEOFF FROM UNDER THE NEUTRAL (BOTTOM LINE) TO A POSITION ABOVE THE NEUTRAL LINE. THE LINEMAN TOUCHED THE SECOND LINE FROM THE BOTTOM WITH HIS ELBOW AND WAS ELECTROCUTED.

Keywords: OVERHEAD POWER LINE, ELECTRICAL, POWER LINE WORKER, PPE, ELECTROCUTED, E PTD, ELEC UTILITY WORK, UTILITY POLE

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 14975312 Fatality Electric Shock Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.