Powered by GoogleTranslate

Inspection Detail

Inspection: 14829378 - T A Beach Corporation

Inspection Information - Office: Department Of Labor, Licensing, And Regulation Division Of Labor And Industry Maryland Occupational Safety And Health

 

Inspection Nr: 14829378
Report ID: 0352440
Date Opened: 10/21/1984

Site Address:
T A Beach Corporation
4647 Forbes Blv
Lanham, MD 20706

Mailing Address:
12331 Carroll Ave, Rockville, MD 20852

Union Status: Union

SIC:1731

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 11/17/1984

Planning Guide: Safety-Construction

Emphasis:

Case Closed: 11/23/1984


Related Activity
Type Activity Nr Safety Health
Accident 360614531
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $390 $0 $0 $0 $0 $390
Current Penalty $390 $0 $0 $0 $0 $390
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19260400 C01 10/26/1984 10/29/1984 $390 $390 $0 -  

Investigation Summary

Investigation Nr: 14210983
Event: 08/21/1984
ELECTRIC SHOCK & BURN - WORK ON EXPOSED ENERGIZED PARTS

AN EMPLOYEE WAS REMOVING TWO SCREWS FROM A BUSBAR IN A 3-PHASE, 208-VOLT, 1200-AMP MAIN DISCONNECT BREAKER BOX USING A 3/8-INCH RATCHET AND SOCKET THAT WERE NOT INSULATED. HE DID NOT TURN OFF THE POWER TO THE BOX. THE RATCHET CAME IN CONTACT WITH THE LIVE BUSBAR, AND HE RECEIVED AN ELECTRIC SHOCK. (THE BOX WAS MANUFACTURED BY FEDERAL PACIFIC.) THE BOLTS HE WAS REMOVING WERE 59 INCHES ABOVE THE FLOOR. THE MAIN SWITCH TO DISCONNECT POWER TO THIS BREAKER PANEL WAS LOCATED 36 INCHES AWAY. THE WRENCH CAUSED AN ARC BETWEEN THE "A" PHASE AND THE "B" PHASE. A SECOND EMPLOYEE WAS NEAR THE PANEL BOX. ALTHOUGH HE WAS NOT INVOLVED IN THE WORK, HE WAS ALSO INJURED. BOTH EMPLOYEES WERE HOSPITALIZED.

Keywords: BURN, ELECTRICAL, ELECTRICIAN, BUSBAR, ELECTRICAL WORK, LOCKOUT, E C, ELECTRIC SHOCK

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 14829378 Hospitalized injury Electric Shock Electricians
2 14829378 Hospitalized injury Electric Shock Supervisors; carpenters and related workers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.