Powered by GoogleTranslate

Inspection Detail

Case Status: CLOSED

Inspection: 1471894.015 - Power Electronics Usa, Inc.

Inspection Information - Office: Bakersfield District Office

 

Inspection Nr: 1471894.015
Report ID: 0950647
Date Opened: 04/07/2020

Site Address:
Power Electronics Usa, Inc.
15241 Lost Hills Rd.
Lost Hills, CA 93249

Mailing Address:
1510 N Hobson St., Gilbert, AZ 85233

Union Status: NonUnion

SIC:

NAICS: 221114 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 09/10/2020

Emphasis:

Case Closed: 10/02/2020


Related Activity
Type Activity Nr Safety Health
Accident 1559818
Inspection 1472213 Yes
Case Status: CLOSED
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $16,200 $0 $0 $0 $0 $16,200
Current Penalty $16,200 $0 $0 $0 $0 $16,200
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citation Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 29400002 B 09/10/2020 09/22/2020 $16,200 $16,200 $0 Z - Issued  

Investigation Summary

Investigation Nr: 129278.015
Event: 03/17/2020
Two employees sustain arc flash burns while preparing to tes

On March 17, 2020, a Service Technician (Employee #1), with the assistance of a second Service Technician (Employee #2), was assigned to repair a fault on an inverter system that was part of a solar power plant. They replaced an Inverter 2.2 (#6) card on the #4 DU Disconnect Switch of the deenergized system. At 5:30 p.m., the system was energized to check the reading from the inverter card inside the cabinet. They found that the card had a bad reading. The employees then started conducting a job briefing in front of the live open panel box in close proximity to energized parts, to determine the next steps of the troubleshooting. They discussed that the cable connection at the card was possibly not making good contact. They were going to disconnect and test the cable. Employee #1 reached in and inadvertently moved the inverter card that was still unscrewed. The card fell off, touching the ground on the inverter and causing an arc flash. The voltage at the system was 690 Volts AC. Employee #1 was not wearing gloves, eye or face protection. Employee #2 was standing next to him and was wearing eye protection but no gloves or face protection. They were both wearing fire resistant clothing. Employee #1 suffered serious first and second degree burns to his face, left hand, and eyes. He was admitted to the hospital for treatment for about a week. Employee #2 received minor burns to the left hand and face. He was treated without hospitalization.

Keywords: Burn, Electric Arc Flash, Electrical Fault, Energized, Eye, Eye protection, Face, Glove, Hand, Panel, Power Plant, Protective Clothing, Reaching, Repair, Service Technician, Troubleshooting

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 1471894.015 24 M Hospitalized injury Electricians
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.