Inspection Detail
Inspection: 14669477 - County Of Kauai-Kapaa Neighborhood Center, Dpw
Inspection Information - Office: Hi-E-Honolulu
Site Address:
County Of Kauai-Kapaa Neighborhood Center, Dpw
Kou St & Kuhio Hwy
Kapaa, HI 96746
Mailing Address:
4396 Rice St, Lihue, HI 96766
Union Status: Union
SIC:7349
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: LocalGovt
Safety/Health: Safety
Close Conference: 10/14/1986
Planning Guide: Safety-Manufacturing
Emphasis:
Case Closed: 12/10/1986
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 360580146 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 1 | 1 | ||||
| Current Violations | 1 | 1 | ||||
| Initial Penalty | $0 | $0 | $0 | $100 | $0 | $100 |
| Current Penalty | $0 | $0 | $0 | $100 | $0 | $100 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Other | 520008 | 11/24/1986 | 10/10/1986 | $100 | $100 | $0 | - |
Investigation Summary
AN EMPLOYEE WAS PERFORMING HIS WEEKLY DUTY OF SCRUBBING A WET CONCRETE FLOOR WITH A 120-VOLT TORNADO FLOOR CLEANING MACHINE (MODEL 283). THE EMPLOYEE RECEIVED AN ELECTRIC SHOCK WHEN HE HELD THE HANDLE OF THE MACHINE. THE ELECTRIC SHOCK CAUSED FIRST DEGREE BURNS, AND THE EMPLOYEE WAS HOSPITALIZED FOR HIS INJURIES. ON INSPECTION, THE RECEPTACLE OUTLET BEING USED TO SUPPLY THE MACHINE WITH ELECTRIC POWER WAS FOUND TO BE WIRED FOR 240 VOLTS, AND THE GROUNDING CONDUCTOR FOR THE OUTLET WAS FOUND TO HAVE 120 VOLTS IMPRESSED ON IT.
Keywords: BURN, RECEPTACLE, ELECTRICAL, E GI VII, GROUND FAULT, ELECTRIC SHOCK, ELEC EQUIPMENT--MISC
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 14669477 | Hospitalized injury | Electric Shock | Occupation not reported |
Translate